Permit: T06CM01268
Permit Details
Status:
C of o
Type:
COMMERCIAL NEW
Address:
7485 E TANQUE VERDE RD
Address NEW:
7485 E TANQUE VERDE RD
Apply Date:
03/03/2006
Applicant:
METRO PERMIT EXPRESS, INC *C
Description:
NEW MEDICAL BUILDING
Contractors:
- VENTURE WEST INC
Permit Reviews
Permit Number - T06CM01268
Permit Status: C of o
Permit Description: NEW MEDICAL BUILDING
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/03/2006 | PLANS OK TO SUBMIT - 3RD PARTY | 03/07/2006 | COMPLETED |
| 03/07/2006 | 3RD PARTY REVIEW-COMMERCIAL | 05/18/2006 | COMPLETED |
| 05/18/2006 | POST 3RD PARTY REVIEW | 06/22/2006 | COMPLETED |
| 06/16/2006 | 3RD PARTY REVIEW-REVISION/OTHER | 06/22/2006 | COMPLETED |
| 08/16/2006 | POST 3RD PARTY REVIEW | 10/23/2006 | COMPLETED |
| 12/14/2006 | 3RD PARTY REVIEW-REVISION/OTHER | 01/03/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM01268
Permit Status: C of o
Permit Description: NEW MEDICAL BUILDING
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/03/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T06CM01268
Permit Description: NEW MEDICAL BUILDING
Total Completed Inspections - 50
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2006 | PLUMBING - PRE SLAB | BBENEDON | Approved | IVRS - Inspection :* |
| 06/24/2006 | PLUMBING - ROUGH, SOIL | BBENEDON | Approved | IVRS - Inspection :* |
| 07/19/2006 | BUILDING PRE-SLAB | JBURGE | Approved | IVRS - Inspection :* |
| 07/20/2006 | EXCAVATION/LAYOUT REBAR & ZON | JBURGE | Approved | IVRS - Inspection :* |
| 08/21/2006 | REINFORCED MASONRY PRE-GROUT | JBURGE | Approved | IVRS - Inspection :* TO 17'10" CAP OFF |
| 09/01/2006 | ROOF NAILING | JBURGE | Approved | IVRS - Inspection :* OK TO DRY IN |
| 09/01/2006 | EXT METAL CLIPS/EXT SHEATHING | JBURGE | Approved | IVRS - Inspection :* OK FOR STUCCO MESH |
| 09/22/2006 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* STRAP UP FLEX DUCTS ABOVE RESTROOMS. PROVIDE A STRAP ON ALL EXHAUST DUCTS. WILL CHECK ON NEXT VISIT. OK FOR SHEETROCK CHECKED CONDENSATE DRAINS. SUSPENDED ROUGH DUCT OK TO PROCEED. |
| 09/27/2006 | STUCCO MESH | JBURGE | Approved | IVRS - Inspection :* OK TO STUCCO |
| 10/03/2006 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :* RECEIVED LETTER FOR M/C CABLE. |
| 10/18/2006 | SHEET ROCK NAILING | JBURGE | Approved | IVRS - Inspection :* OK TO TAPE THROUGHOUT |
| 10/18/2006 | FRAMING | JBURGE | Approved | IVRS - Inspection :* |
| 11/09/2006 | BUILDING - PROGRESS | JBURGE | Approved | IVRS - Inspection :* NEW SOFFIT IN RECEPTION AREA - SHEETROCKED OK TO TAPE & TEXTURE. |
| 11/15/2006 | BUILDING ABOVE CEILING | JBURGE | Approved | IVRS - Inspection :* OK TO SET TILES |
| 11/22/2006 | PLUMBING - PROGRESS | BBENEDON | Approved | I AM PLEASED WITH YOUR FLANGE EXTENSION, FLANAGES INSTALLED AT THE HEIGHT REQUIRED BY THE UPC-PROVIDES A BETTER PRODUCT FOR THE CONSUMER NOTE: YOUR FLANGES WERE APPROVED ON 9/29 |
| 11/22/2006 | TEP CLEARANCE - AM | JWEATHER | Approved | TMPP CLEARED PER R. HOLLANDER |
| 12/12/2006 | FIRE - FINAL | LTHOMAS | Approved | |
| 12/12/2006 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 12/13/2006 | ELECTRIC - UFER | RHOLLAND | Approved | IVRS - Inspection :* 1. MAINTAIN WORKING CLEARANCES IN FRONT OF PANEL "B" 110.26 2. CLEARLY LABEL BREAKER 3. BOND WIRE MOLD RACEWAYS 4. FRONT DOOR EXIT NOT WORKING |
| 12/13/2006 | OUTDOOR LIGHTING FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
| 12/13/2006 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection :* |
| 12/13/2006 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
| 12/13/2006 | NPPO - FINAL | ACONNOR | Approved | N/A |
| 12/13/2006 | LANDSCAPE - FINAL | ACONNOR | Approved | |
| 12/14/2006 | ENGINEERING - FINAL | JBRUCKME | Approved | |
| 12/14/2006 | ENGINEERING - FINAL | JBRUCKME | Approved | 1. PROVIDE HANDICAP PARKING SIGNS AND REPAIR TRUNCATED DOME PAVERS. 2. COMPLETE SIDEWALK SCUPPER AND DEPRESS ROCK RIP RAP SWALES. 3. CLEAN UP CONSTRUCTION MATERIAL AND DEBRIS, AND CLEAN MORTAR OFF CURBS. 4. PROVIDE BICYCLE PARKING |
| 12/15/2006 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* |
| 12/15/2006 | MECHANICAL - HOODS | JMILITEL | Approved | IVRS - Inspection :* |
| 12/15/2006 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* |
| 12/15/2006 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* UNLISTED EQUIPMENT TO BE REMOVED OK FINAL RECEIVED CHECK #26390 #108.00 |
| 12/15/2006 | BUILDING - FINAL | JBURGE | Approved | IVRS - Inspection :* ADJUST HC PARKING SIGNS TO 84" @ BOTTOM OF SIGN TO GROUND LEVEL. |
| 12/15/2006 | ELECTRIC - TEMP POWER FOR TEST | RHOLLAND | Approved | IVRS - Inspection :* |
| 12/15/2006 | ELECTRIC - OUTDOOR LIGHTING | RHOLLAND | Approved | IVRS - Inspection :* |
| 12/15/2006 | ELECTRIC - ABOVE CEILING | RHOLLAND | Approved | IVRS - Inspection :* |
| 12/15/2006 | U VALUE FOR WINDOW | JBURGE | Approved | IVRS - Inspection :* |
| 12/15/2006 | PLUMBING - ABOVE CEILING | BBENEDON | Approved | IVRS - Inspection :* |
| 12/15/2006 | PLUMBING - INTERMEDIATE | BBENEDON | Approved | IVRS - Inspection :* |
| 12/15/2006 | PLUMBING - YARD WTR LINE/TEST | BBENEDON | Approved | IVRS - Inspection :* |
| 12/15/2006 | SITE - SEWER | BBENEDON | Approved | IVRS - Inspection :* |
| 12/15/2006 | RIGHT OF WAY - FINAL | PWHIDDON | Approved | PER EMAIL |
| 12/19/2006 | PLUMBING - FINAL | BBENEDON | Approved | IVRS - Inspection :* |
| 12/20/2006 | ELECTRIC - CONSTRUCTION POWER | RHOLLAND | Approved | |
| 12/20/2006 | ELECTRIC - TEMPORARY SERVICE | RHOLLAND | Approved | |
| 12/20/2006 | ELECTRIC - RECONNECT | RHOLLAND | Approved | |
| 12/20/2006 | ELECTRIC - SERVICE UPGRADE | RHOLLAND | Approved | |
| 12/20/2006 | ELECTRIC - PROGRESS | RHOLLAND | Approved | |
| 12/20/2006 | ELECTRIC - TEMPORARY POLE | RHOLLAND | Approved | |
| 12/20/2006 | ELECTRIC - CABLE DROP | RHOLLAND | Approved | |
| 12/20/2006 | ELECTRIC - SERVICE RELOCATION | RHOLLAND | Approved | |
| 12/20/2006 | STEM WALL/RETAINING WALL | JBURGE | Approved |