Permit: T06CM01268

Parcel: 114600780

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/19/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
12/18/2006 PLUMBING - FINAL Partial Approval ONLY ISSUES REMAINING ARE:
1. INSTALLATION INSTRUCTIONS FOR NEUTRALIZATION TANKS
2. TERMINATION OF ROOF DRAINS
3. CHECK VALVE INSTALLED BETWEEN EXPANSION TANK AND WH IS NOT PER PLAN AND PREVENTS THE EFFECTIVENESS OF THE EXPANSION TANK.

I SEE NO HAZARDS THAT WOULD PREVENT A TCO
12/14/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PLAN REVISION FOR AAV AT P-6
2. CHECK AT RECIRC PUMP
3. NEUTRALIZING TANK INSTALLATION INSTRUCTIONS
FOR P-6 (P-10)
4. ROOF DRAINS MISSING STRAINER.
12/13/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- PROVIDE REVISION FOR USE OF AAV'S AT P-6 LOCATIONS AS REQUESTED ON 9/29
- PROVIDE P2 DETAIL FOR RECIRC PUMP OR MANUFACTURES INSTALLATION INSTRUCTIONS.
- PROVIDE DETAIL FOR NEUTRALIZING TANK
PROVIDE PLUMBING SPECS
PROVIDE ACCESS TO ROOF