Permit Details

Status:
Closed
Type:
COMMERCIAL OTHER
Address:
7960 E 22ND ST
Apply Date:
01/17/2006
Applicant:
SWAN WAYNE E
Description:
RELOCATE GENERATOR
Contractors:
  • PATIO POOLS & SPAS *P *C

Permit Reviews

Permit Number - T06CM00274
Permit Status: Closed
Permit Description: RELOCATE GENERATOR
Start Date Submittal Complete Date Status  
01/17/2006 OTHER 03/01/2006 COMPLETED Review Details
03/01/2006 COMMERCIAL-BLDG/FIRE/ZONING/ENG 03/02/2006 COMPLETED Review Details
03/07/2006 COMMERCIAL-BLDG/FIRE/ZONING/ENG 03/09/2006 COMPLETED Review Details
08/25/2006 REVISION - - 1ST 08/25/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM00274
Permit Status: Closed
Permit Description: RELOCATE GENERATOR
Total Outstanding Activity Conditions - 1
Date Name
01/17/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Closed
Permit Number: T06CM00274
Permit Description: RELOCATE GENERATOR
Total Completed Inspections - 8
Date Description Inspector Results Comments
08/07/2006 PLUMBING - GAS PRESSURE TEST RRICH Approved IVRS - Inspection :*
14 PSI TEST FROM METER TO GENERATOR SHUT OFF VALVE OK
03090 -
1. PROVIDE PIPING PER GAS TRAIN DETAIL TO MEET NFPA 37
2. PROVIDE A LISTED GAS FLEX FOR THIS ENGINE I DON'T THINK A PIECE OF HOSE & (2) WORM GEAR CLAMPS MEETS THE REQUIREMENT.
08/09/2006 ELECTRIC - OUTDOOR LIGHTING RSUBA Approved IVRS - Inspection :*
08/09/2006 ELECTRIC - UNDERGROUND RSUBA Approved IVRS - Inspection :*
08/24/2006 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection :*
PLASTIC BUSH AT SEAL TIGHT CONNECTION
08/24/2006 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection :*
09/01/2006 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
09/01/2006 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
1. REVISED GAS TRAIN DETAIL ON SITE
2. OK FOR GAS
3. PLUMBER TO DO SOAP TEST FINAL CONNECTION
4. GAS IS ON
01/22/2009 FIRE - FINAL FIRE Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW