Permit: T06CM00274
Permit Details
Apply Date:
01/17/2006
Applicant:
SWAN WAYNE E
Description:
RELOCATE GENERATOR
Contractors:
- PATIO POOLS & SPAS *P *C
Permit Reviews
Permit Number - T06CM00274
Permit Status: Closed
Permit Description: RELOCATE GENERATOR
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/17/2006 | OTHER | 03/01/2006 | COMPLETED |
03/01/2006 | COMMERCIAL-BLDG/FIRE/ZONING/ENG | 03/02/2006 | COMPLETED |
03/07/2006 | COMMERCIAL-BLDG/FIRE/ZONING/ENG | 03/09/2006 | COMPLETED |
08/25/2006 | REVISION - - 1ST | 08/25/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM00274
Permit Status: Closed
Permit Description: RELOCATE GENERATOR
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
01/17/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Closed
Permit Number: T06CM00274
Permit Description: RELOCATE GENERATOR
Total Completed Inspections - 8
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/07/2006 | PLUMBING - GAS PRESSURE TEST | RRICH | Approved | IVRS - Inspection :* 14 PSI TEST FROM METER TO GENERATOR SHUT OFF VALVE OK 03090 - 1. PROVIDE PIPING PER GAS TRAIN DETAIL TO MEET NFPA 37 2. PROVIDE A LISTED GAS FLEX FOR THIS ENGINE I DON'T THINK A PIECE OF HOSE & (2) WORM GEAR CLAMPS MEETS THE REQUIREMENT. |
08/09/2006 | ELECTRIC - OUTDOOR LIGHTING | RSUBA | Approved | IVRS - Inspection :* |
08/09/2006 | ELECTRIC - UNDERGROUND | RSUBA | Approved | IVRS - Inspection :* |
08/24/2006 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection :* PLASTIC BUSH AT SEAL TIGHT CONNECTION |
08/24/2006 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection :* |
09/01/2006 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* |
09/01/2006 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* 1. REVISED GAS TRAIN DETAIL ON SITE 2. OK FOR GAS 3. PLUMBER TO DO SOAP TEST FINAL CONNECTION 4. GAS IS ON |
01/22/2009 | FIRE - FINAL | FIRE | Approved |