Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T06CM00274
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/07/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 14 PSI TEST FROM METER TO GENERATOR SHUT OFF VALVE OK 03090 - 1. PROVIDE PIPING PER GAS TRAIN DETAIL TO MEET NFPA 37 2. PROVIDE A LISTED GAS FLEX FOR THIS ENGINE I DON'T THINK A PIECE OF HOSE & (2) WORM GEAR CLAMPS MEETS THE REQUIREMENT. |
|
07/13/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TEST SHALL HOLD PRESSURE WITH NO LOSS. 2. COMPLETE PIPING TO UNIT. 3. PROVIDE TEST GAUGE IN 1/10 POUND INCREMENTS. |