Permit: T06CM00274

Parcel: 13602001G


Addresses:

7960 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM00274

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/24/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/23/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/09/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL HORIZONTAL GFI WEATHERPROOF RECEPTACLE COVER.
2. INSTALL PLASTIC BUSHING ON 1 1/2" RIGID 90 DEG. AT JBOX
3. INSTALL BOND BUSHING AT PANEL PPIT TO ASSURE PROPER CONDUIT BONDING.
4. SECURE 1 1/2" E.M.T WITHIN 3' OF PANEL & 1/2" & 1" CONDUITS.