Permit: T05EL00558
Permit Details
Apply Date:
03/23/2005
Applicant:
LUGO S WIRING *T
Description:
INSTALL:NEW METER
Contractors:
- LUGO S WIRING *T
Permit Reviews
Permit Number - T05EL00558
Permit Status: Final
Permit Description: INSTALL:NEW METER
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/23/2005 | ELECTRICAL | 03/24/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05EL00558
Permit Status: Final
Permit Description: INSTALL:NEW METER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/23/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T05EL00558
Permit Description: INSTALL:NEW METER
Total Completed Inspections - 5
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2005 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection :* OK UNDERGROUND OK TO CLEAR ECO 2M NO BOND REQUIRED. CALL FOR FINAL WHEN DONE WITH FINAL EQUIP CONNECTION. |
| 04/29/2005 | TEP CLEARANCE - AM | JKOZUCH | Approved | ECO 2M |
| 05/19/2005 | ELECTRIC - FINAL | DSANTACR | Approved | 1) EQUIP GROUND TO BAILER MACH. CANNOT BE TERMINATED ON NEUTRAL BAR IN SERVICE DISCONNECT, INSTALL EQUIP GROUND BAR IN SERVICE DISCONNECT & GROUND TO BAR-NOTE THAT GROUND WIRE TO EQUIP TO BE COLOR CODED GREEN. |
| 05/20/2005 | ELECTRIC - UNDERGROUND | MCAPISTR | Approved | |
| 05/23/2005 | PERMIT FINALED | JWEATHER | Approved |