Permit: T05EL00558

Parcel: 124160200


Addresses:

650 E 22ND ST 2M

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/28/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :* OK UNDERGROUND OK TO CLEAR ECO 2M NO BOND REQUIRED. CALL FOR FINAL WHEN DONE WITH FINAL EQUIP CONNECTION.
04/12/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*NOTES: 1) SERVICE DISCONNECT NOT RATED 480V. 2) FUSED MUST BE INSTALLED WITH REJECTION PINS. 3) EQUIP. SUPPLIED BY SERVICE NOT CONNECTED. EQUIP. TO BE CONNECTED MUST HAVE UL LISTING