Permit: T05EL00558

Parcel: 124160200


Addresses:

650 E 22ND ST 2M

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/19/2005 ELECTRIC - FINAL Approved 1) EQUIP GROUND TO BAILER MACH. CANNOT BE TERMINATED ON NEUTRAL BAR IN SERVICE DISCONNECT, INSTALL EQUIP GROUND BAR IN SERVICE DISCONNECT & GROUND TO BAR-NOTE THAT GROUND WIRE TO EQUIP TO BE COLOR CODED GREEN.
05/18/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*