Permit: T05CM05329
Permit Details
Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
3525 N CAMPBELL AV
Address NEW:
3525 N CAMPBELL AV
Apply Date:
10/19/2005
Applicant:
N/A
Description:
TI:APPLIANCE STORE
Architects:
- STICKLEY DESIGN GROUP
Contractors:
- AZ BUILDERS AND MAINTENANCE COMPANY INC
Permit Reviews
Permit Number - T05CM05329
Permit Status: C of o
Permit Description: TI:APPLIANCE STORE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/19/2005 | COMMERCIAL TI | 10/26/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM05329
Permit Status: C of o
Permit Description: TI:APPLIANCE STORE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/19/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T05CM05329
Permit Description: TI:APPLIANCE STORE
Total Completed Inspections - 21
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2005 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* |
| 12/07/2005 | ELECTRIC - INTERMEDIATE | CCLEMENS | Approved | IVRS - Inspection : The service is not per code.| 210* 1. NEED MAIN BONDING JUMPERS IN SERVICE DISCONNECT ENCLOSURES 2. PROVIDE ACCESS TO ROOF AND FEEDER PULL BOXES 3. HAVE ELECTRICIAN ON SITE @ TIME OF INSPECTION TO OPEN RACEWAYS |
| 12/13/2005 | STUCCO MESH | AQUIROZ | Approved | IVRS - Inspection :* |
| 12/13/2005 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :* 1. CALL 03040 YARDWATER FOR OUTSIDE INSPECTION 2. REVISED PLAN ON SITE OK TO COVER ALL AREAS |
| 12/13/2005 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* |
| 12/14/2005 | PLUMBING - ABOVE CEILING | RMYERS | Approved | IVRS - Inspection :* 1. ABOVE CEILING OK 2. YARDWATER INSTALLED - CONTRACTOR TO REDLINE CHANGES - OK TO COVER, SUBJECT TO LISTING OF SOLVENT CEMENT. |
| 12/14/2005 | PLUMBING - YARD WTR LINE/TEST | RMYERS | Approved | IVRS - Inspection :* |
| 12/15/2005 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
| 12/29/2005 | RIGHT OF WAY - FINAL | MOTERO | Approved | PER EMAIL |
| 12/29/2005 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :*ON FINAL REPAIR ALL BROKEN DRAIN PANS & DRAIN LINES ON A/C UNITS PROVIDE SOUND ALTERNATORS FOR A/C 4 AS PER PLANS PROVIDE FRESH AIR INTAKES |
| 12/29/2005 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* |
| 12/29/2005 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* TEMP C/O; MUST FINAL ELEC ON INSTALLED SIGNS; T05OT02872 BEFORE FINAL C/O CAN BE ISSUED |
| 12/29/2005 | ELECTRIC - ABOVE CEILING | RHOLLAND | Approved | IVRS - Inspection :* ROOF: 1. FINISH CONNECTIONS PER A/C UNIT 2. TIGHTEN LOOSE FITTINGS BUILDING: 1. BOXES NOT TO HAVE MORE THAN 1/8" OPEN AROUND BOXES 314/21 2. GROUND JUNCTION BOXES 3. SUPPORT WIRES NEEDED FOR FIXTURES 4. SUPPORT FLEX CONDUIT ABOVE CEILING 5. SUPPORT VDV CABELING AS PER 800.6 & 225.6 6. FINISH CABLE TRAY AND SECURE AS PER CODES 7. PLANS CALL FOR 3/4" MIN CONDUIT ONLY PLEASE PROVIDE LETTER FOR SMALLER CONDUIT AND M/C CABLE 8. PLEASE VERIFY DIMMER DERATING FOR MULTI-GANG INSTALLATION 9. BOND CABLE TRAY 10. #4 & LARGER PROTECT CONDUCTOR AT FITTINGS 11. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 12. EXTENDER RINGS AT COMBUSTIBLE SURFACES 13. INSTALL SECONDARY CONDUCTOR PER 230.7 14. INSTALL GROUNDING ELECTRODE SYSTEM |
| 12/29/2005 | ENGINEERING - FINAL | DROBERTS | Approved | INSTALL THE TRUNCATED DOMES AT THE HANDICAP ACCESS RAMP AS SHOWN ON THE APPROVED PLANS, AND COMPLETE ALL EXTERIOR WORK INCLUDING THE CLEANUP. |
| 12/29/2005 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
| 12/29/2005 | ELECTRIC - OUTDOOR LIGHTING | RHOLLAND | Approved | IVRS - Inspection :* |
| 12/29/2005 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* |
| 12/29/2005 | PLUMBING - PROGRESS | RMYERS | Approved | IVRS - Inspection :* |
| 12/29/2005 | FIRE - FINAL | LLAKEY | Approved | EXIT DOORS MUST SWING IN DIRECTION OF EGRESS |
| 01/06/2006 | BUILDING - FINAL | AQUIROZ | Approved | AFTER HOURS INSPECTION CK # 7586 $ 108.00 |
| 01/06/2006 | PERMIT FINALED | CCLEMENS | Approved |