Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/29/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* ROOF: 1. FINISH CONNECTIONS PER A/C UNIT 2. TIGHTEN LOOSE FITTINGS BUILDING: 1. BOXES NOT TO HAVE MORE THAN 1/8" OPEN AROUND BOXES 314/21 2. GROUND JUNCTION BOXES 3. SUPPORT WIRES NEEDED FOR FIXTURES 4. SUPPORT FLEX CONDUIT ABOVE CEILING 5. SUPPORT VDV CABELING AS PER 800.6 & 225.6 6. FINISH CABLE TRAY AND SECURE AS PER CODES 7. PLANS CALL FOR 3/4" MIN CONDUIT ONLY PLEASE PROVIDE LETTER FOR SMALLER CONDUIT AND M/C CABLE 8. PLEASE VERIFY DIMMER DERATING FOR MULTI-GANG INSTALLATION 9. BOND CABLE TRAY 10. #4 & LARGER PROTECT CONDUCTOR AT FITTINGS 11. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 12. EXTENDER RINGS AT COMBUSTIBLE SURFACES 13. INSTALL SECONDARY CONDUCTOR PER 230.7 14. INSTALL GROUNDING ELECTRODE SYSTEM |
|
| 11/23/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*NOTE: OK TO COVER SIGN CONDUIT IN PARKING LOT ( BLDG TO SIGN) |