Permit Number: T05CM05329
Parcel: 11305064A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05329
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2005 LOREN MAKUS ENGINEERING REVIEW Approved
10/19/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/19/2005 TERRY STEVENS ZONING REVIEW Approved
10/19/2005 ROBERT SHERRY WATER REVIEW Approved
10/24/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/25/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/25/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM05329 10/19/05

THIS IS AN INCOMPLETE REVIEW. ONLY HAD THE OPPORTUNITY TO CHECK LIGHTING AND RECEPTACLE BRANCH CIRCUITS, AND COMMENT, WITHIN OVER-THE-COUNTER TIME FRAME.

It appears that the following branch circuits should be circuited as follows:
A-22, 0.4 not 0.1 VA
A-26, 0.3 not 0.1 VA
B-5, 0.9, not 0.7 VA
B-8, B-9, B-9, B-10, B-19, B-21, B-25, B-26, B-27, B-28, B-30, 0.7 not 0.5 VA
B-7, B-20, 0.5 not 0.4 VA
B-12, 0.4 not 0.3 VA

Please correct the above and submit plans for review, not over the counter.
10/26/2005 GERRY KOZIOL WWM REVIEW Approved
10/26/2005 JIM EGAN FIRE REVIEW Approved