Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05329
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 10/19/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/19/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 10/19/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/24/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/25/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/25/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM05329 10/19/05 THIS IS AN INCOMPLETE REVIEW. ONLY HAD THE OPPORTUNITY TO CHECK LIGHTING AND RECEPTACLE BRANCH CIRCUITS, AND COMMENT, WITHIN OVER-THE-COUNTER TIME FRAME. It appears that the following branch circuits should be circuited as follows: A-22, 0.4 not 0.1 VA A-26, 0.3 not 0.1 VA B-5, 0.9, not 0.7 VA B-8, B-9, B-9, B-10, B-19, B-21, B-25, B-26, B-27, B-28, B-30, 0.7 not 0.5 VA B-7, B-20, 0.5 not 0.4 VA B-12, 0.4 not 0.3 VA Please correct the above and submit plans for review, not over the counter. |
| 10/26/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/26/2005 | JIM EGAN | FIRE | REVIEW | Approved |