Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T05CM04568
Permit Details
Apply Date:
09/02/2005
Applicant:
STEVE OLSEN (SPRING)
Description:
NEW WIRELESS COMM. FACILITY
Contractors:
- ARIZONA WEST BUILDERS AND COMMUNICATIONS INC
Permit Reviews
Permit Number - T05CM04568
Permit Status: Final
Permit Description: NEW WIRELESS COMM. FACILITY
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
09/02/2005 | PLANS OK TO SUBMIT - COMM | 09/16/2005 | COMPLETED |
09/02/2005 | PLANS OK TO SUBMIT - SITE | 09/16/2005 | COMPLETED |
09/16/2005 | CELL TOWER/ANTENNAS | 10/14/2005 | COMPLETED |
09/16/2005 | SITE | 10/07/2005 | COMPLETED |
10/07/2005 | RESUBMITTAL | 10/14/2005 | COMPLETED |
10/21/2005 | RESUBMITTAL | 11/09/2005 | COMPLETED |
11/09/2005 | 3RD PARTY REVIEW-COMMERCIAL | 12/01/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM04568
Permit Status: Final
Permit Description: NEW WIRELESS COMM. FACILITY
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
09/02/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T05CM04568
Permit Description: NEW WIRELESS COMM. FACILITY
Total Completed Inspections - 7
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/22/2005 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection :*GROUNDING NOT READY POWER SUPPLY NOT READY FINAL CAN COVER ALL ITEMS |
01/19/2006 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | IVRS - Inspection :* |
01/20/2006 | ELECTRIC - SERVICE RELOCATION | RMAJUTA | Approved | OK TO CLEAR CABLE DROP 50 KVA TRANSFORMER NEED WEATHERPROOF SHIELDS 2" FLEX FITTING FROM TRANSFORMER TO PPC NEEDS PLASTIC BUSHING 2" CONNECTOR INTO PPC NEEDS BUSHING INSIDE PPC CABINET 4/0 COPEPR CONDUCTORS REQUIRE A PLASTIC BUSHING OR CHASE NIPPLE |
01/25/2006 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection :*OK TO CLEAR ECO QUARTZ LIGHT TO REMAIN FULLY SHIELDED |
01/26/2006 | TEP CLEARANCE - AM | RMAJUTA | Approved | ECO |
02/09/2006 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* |
02/09/2006 | BUILDING - PROGRESS | AQUIROZ | Approved | IVRS - Inspection :* |