Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
Permit Number - T05CM04568
Inspection Description - ELECTRIC - SERVICE RELOCATION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/20/2006 | ELECTRIC - SERVICE RELOCATION | Approved | OK TO CLEAR CABLE DROP 50 KVA TRANSFORMER NEED WEATHERPROOF SHIELDS 2" FLEX FITTING FROM TRANSFORMER TO PPC NEEDS PLASTIC BUSHING 2" CONNECTOR INTO PPC NEEDS BUSHING INSIDE PPC CABINET 4/0 COPEPR CONDUCTORS REQUIRE A PLASTIC BUSHING OR CHASE NIPPLE |