Permit Number: T05CM04568
Parcel: 11627504B

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T05CM04568
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2005 GLENN MOYER PLANNING-CITY HALL REVIEW Approved
09/27/2005 DAN CASTRO ZONING REVIEW Approved Site plan must be approved prior to building plan approval. Site plan is currently under review.
10/03/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 10/4/05
ACTIVITY NUMBER: T05CM04568
PROJECT NAME: Cell Tower
PROJECT ADDRESS: New wireless facility
ARCHITECT / ENGINEER: Young Design Corp.
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Engineer that has provided structural calculations needs to stamp the drawings that refer to items that are being justified per structural calculations. This will clarify that engineer has reviewed site and is aware of all conditions.
2)Provide connection details for antennas mounted on light pole and parking structure wall.
3)Sht. A-2 detail 3 typical PPC elevation specifies equipment weighs 400 lbs and structural calculation sht. #2 specifies 300 lbs. Please clarify.
4)Provide structural calculations justifying existing structure can support additional dead load. Added equipment cannot use the designed live load for justification.
5) Special Inspection form will be required for Epoxy Anchors before permit can be issued.
10/07/2005 LOREN MAKUS ENGINEERING REVIEW Approved
10/10/2005 JAY HOGAN OPERATIONS REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/14/2005 CINDY AGUILAR OUT TO CUSTOMER Completed