Permit: T05CM02744
Permit Details
Apply Date:
06/14/2005
Applicant:
BOBBY OTERO
Description:
REMODEL FIRE DAMAGE:SFR
Permit Reviews
Permit Number - T05CM02744
Permit Status: Final
Permit Description: REMODEL FIRE DAMAGE:SFR
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
05/04/2012 | REVISION - - 5TH | 08/08/2012 | COMPLETED |
05/25/2011 | REVISION - - 3RD | 05/25/2011 | COMPLETED |
06/14/2005 | PLANS OK TO SUBMIT - RES 3RD PARTY | 06/15/2005 | COMPLETED |
06/15/2005 | 3RD PARTY REVIEW-RESIDENTIAL | 07/07/2005 | COMPLETED |
06/27/2013 | REVISION - 10TH | 06/27/2013 | COMPLETED |
07/07/2005 | POST 3RD PARTY REVIEW | 07/22/2005 | COMPLETED |
07/22/2005 | RESUBMITTAL | 07/22/2005 | COMPLETED |
08/08/2012 | REVISION - - 6TH | 08/08/2012 | COMPLETED |
08/21/2012 | REVISION - - 6TH | 08/21/2012 | COMPLETED |
08/29/2012 | REVISION - - 7TH | 08/29/2012 | COMPLETED |
09/11/2012 | REVISION - - 8TH | 09/12/2012 | COMPLETED |
09/16/2005 | 3RD PARTY REVIEW-REVISION/OTHER | 09/16/2005 | COMPLETED |
10/03/2012 | REVISION - - 9TH | 11/08/2012 | COMPLETED |
10/05/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 10/05/2007 | COMPLETED |
11/07/2012 | REVISION - WALK THRU | 11/08/2012 | COMPLETED |
11/14/2011 | REVISION - - 4TH | 11/14/2011 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM02744
Permit Status: Final
Permit Description: REMODEL FIRE DAMAGE:SFR
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/14/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T05CM02744
Permit Description: REMODEL FIRE DAMAGE:SFR
Total Completed Inspections - 27
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2005 | ELECTRIC - TEMP POWER FOR TEST | ROHAVER | Approved | IVRS - Inspection :* |
08/16/2005 | TEP CLEARANCE - AM | FGREER | Approved | ECO CLEARED BY OHAVER |
12/08/2005 | ROOF NAILING | RCAMACHO | Approved | IVRS - Inspection :* 1) EXCEPT EXISTING FRONT PORCH AND REAR BATHROOM |
12/08/2005 | FRAMING | RCAMACHO | Approved | IVRS - Inspection :* |
12/08/2005 | EXT METAL CLIPS/EXT SHEATHING | RCAMACHO | Approved | IVRS - Inspection :* |
05/11/2006 | ELECTRIC - CONSTRUCTION POWER | ROHAVER | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL DEADFRONTS BOTH SIDES. 2. INSTALL BREAKER TO FEED GFCI OUTLETS. 3. UNDERSIZED GROUNDING ELECTRODE CONDUCTOR 4. UNDERSIZED GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS FROM GROUND ROD TO GROUND INTO PANEL. 5. CLAMPS LOOSE ON GROUND RODS. 6. GROUND RODS TO BE MINIMUM 6' APART. 7. NO PLANS 8. STOPPED INSPECTION. |
05/11/2006 | ELECTRIC - RECONNECT | ROHAVER | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
07/18/2006 | ELECTRIC - SERVICE UPGRADE | ROHAVER | Approved | IVRS - Inspection :* |
10/08/2007 | STUCCO MESH | CRUIZ | Approved | IVRS - Inspection :* |
11/30/2011 | PLUMBING - YARD WTR LINE/TEST | LHANLY | Approved | HOSE BIBBS & NEW PIPE AT SE CORNER OK. NEED ANTI-SIPHON DEVICES ON HOSE BIBBS BEFORE FINAL |
11/30/2011 | PLUMBING - INTERMEDIATE | LHANLY | Approved | |
10/16/2012 | EXCAVATION/LAYOUT REBAR & ZON | LHANLY | Approved | |
11/07/2012 | MECHANICAL - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* |
11/07/2012 | ELECTRIC - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* |
11/29/2012 | SHEET ROCK NAILING | MPUGH | Approved | IVRS - Inspection :* |
06/25/2013 | BUILDING - FINAL | RCAMACHO | Approved | 1. SECURE #4 TO BUILDING @ PANEL 2. WHITE HOT LEADS TO BE RED OR BLACK (TAPE OK) 3. PROVIDE PROOF OF 3050 APPROVAL 4. EXTERIOR FIXTURES NOT UNDER ROOF TO BE SHIELDED 5. SEC PANEL LEAD CONDUCTORS NOT TO EXIT TOP WALL 6. STOOP EXIT DOORS 7. PROTECT LINE SET FROM ELEMENTS 8. PAINT ROOF VENTS 9. PROVIDE GAS BOND 10 PANEL "B" NOT ALLOWED IN CLOSET. NOT INSTALLED TO PLAN LOCATION 11. GFCI @ MASTER BATH DOES NOT TEST 9. PROVIDE GAS BOND |
06/25/2013 | OUTDOOR LIGHTING FINAL | RCAMACHO | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
06/25/2013 | MECHANICAL - FINAL | RCAMACHO | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
06/25/2013 | PLUMBING - FINAL | RCAMACHO | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
06/25/2013 | BUILDING - FINAL | RCAMACHO | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
06/28/2013 | PLUMBING - GAS RECONNECT | RMYERS | Approved | |
06/28/2013 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | |
06/28/2013 | PLUMBING - GAS PRESS TEST FNL | RMYERS | Approved | |
08/14/2013 | ELECTRIC - FINAL | MPUGH | Approved | IVRS - Inspection :* |
01/08/2014 | ELECTRIC - OUTDOOR LIGHTING | RMYERS | Approved | |
01/08/2014 | ELECTRIC - UNDERGROUND | RMYERS | Approved | |
01/08/2014 | U VALUE FOR WINDOW | RMYERS | Approved |