Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
Permit Number - T05CM02744
Inspection Description - ELECTRIC - CONSTRUCTION POWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2014 | ELECTRIC - CONSTRUCTION POWER | Approved | ||
05/11/2006 | ELECTRIC - CONSTRUCTION POWER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL DEADFRONTS BOTH SIDES. 2. INSTALL BREAKER TO FEED GFCI OUTLETS. 3. UNDERSIZED GROUNDING ELECTRODE CONDUCTOR 4. UNDERSIZED GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS FROM GROUND ROD TO GROUND INTO PANEL. 5. CLAMPS LOOSE ON GROUND RODS. 6. GROUND RODS TO BE MINIMUM 6' APART. 7. NO PLANS 8. STOPPED INSPECTION. |