Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/08/2014 | BUILDING - FINAL | Approved | ||
| 06/25/2013 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/25/2013 | BUILDING - FINAL | Denied | 1. SECURE #4 TO BUILDING @ PANEL 2. WHITE HOT LEADS TO BE RED OR BLACK (TAPE OK) 3. PROVIDE PROOF OF 3050 APPROVAL 4. EXTERIOR FIXTURES NOT UNDER ROOF TO BE SHIELDED 5. SEC PANEL LEAD CONDUCTORS NOT TO EXIT TOP WALL 6. STOOP EXIT DOORS 7. PROTECT LINE SET FROM ELEMENTS 8. PAINT ROOF VENTS 9. PROVIDE GAS BOND 10 PANEL "B" NOT ALLOWED IN CLOSET. NOT INSTALLED TO PLAN LOCATION 11. GFCI @ MASTER BATH DOES NOT TEST 9. PROVIDE GAS BOND |