Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Apply Date:
05/12/2005
Applicant:
N/A
Description:
FIRE DAMAGE REPAIR FIRE DAMAGE # T05VL00388
Architects:
  • 3D ARCHITECTURAL DESIGNS
Contractors:
  • CASAS LINDAS DEVELOPMENT CORP ,

Permit Reviews

Permit Number - T05CM02165
Permit Status: Final
Permit Description: FIRE DAMAGE REPAIR FIRE DAMAGE # T05VL00388
Start Date Submittal Complete Date Status  
05/12/2005 OTHER 09/27/2005 COMPLETED Review Details
09/27/2005 3RD PARTY REVIEW-COMMERCIAL 10/05/2005 COMPLETED Review Details
10/06/2005 POST 3RD PARTY REVIEW 10/18/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM02165
Permit Status: Final
Permit Description: FIRE DAMAGE REPAIR FIRE DAMAGE # T05VL00388
Total Outstanding Activity Conditions - 1
Date Name
05/12/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T05CM02165
Permit Description: FIRE DAMAGE REPAIR FIRE DAMAGE # T05VL00388
Total Completed Inspections - 27
Date Description Inspector Results Comments
10/24/2005 BUILDING ABOVE CEILING AMATHIES Approved IVRS - Inspection :*FIRE CAULK ALL PENETRATIONS IN FIRE WALLS.
11/08/2005 ELECTRIC - RECONNECT DSANTACR Approved INSTALL NEW OR REPAIR SMOKE DETECTORS
11/09/2005 TEP CLEARANCE - AM JWEATHER Approved RECON FOR UNITS #135, 335, 141, 431, 136, 336, 142 AND 342 PER D. SANTACRUZ
11/16/2005 PLUMBING - FINAL BBENEDON Approved IVRS - Inspection :*
1) UNITS 135, 136, 335, 336, 141, 142, 342 AND 341 ARE INTACT AS ORIGINALLY CONSTRUCTED
2) NOTE: SHOWER DIVERTERS ARE NOT ANTI-SCALD BUT DO MEET CODE STANDARDS APPLICABLE TO ORIGINAL CONSTRUCTION
3) OK FOR TEMP C OF O PER S. LONG
11/16/2005 FIRE - FINAL LLAKEY Approved APPROVED FOR UNITS 135,136,141,142,335,336,341,&342 ONLY
11/17/2005 EXT METAL CLIPS/EXT SHEATHING AMATHIES Approved IVRS - Inspection :*
11/22/2005 MECHANICAL - ABOVE CEILING JMILITEL Approved INSULATE ALL SIDEWALL & CEILING REGISTER BOXES ON 2ND FLOOR.
PROVIDE FHA PLATE STRAPS UNDER CONDENSATE DRAIN LINES.
REMOVE PVC FROM RETURN AIR PLENUMS. CPVC IS OK
RECALL FOR INSPECTION
11/23/2005 BUILDING - PROGRESS AMATHIES Approved IVRS - Inspection :* DO NOT LEAVE PAPER BACKED INSULATION EXPOSED. FRIAME TENNANT SEPARATION WALLS TO BOTTOM OF DECK & ROOF
11/23/2005 ELECTRIC - ABOVE CEILING DSANTACR Approved IVRS - Inspection :*
11/23/2005 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection :*
11/23/2005 ROOF NAILING AMATHIES Approved IVRS - Inspection :*
11/29/2005 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :*NEED TO ISOLATE ALL REFRIG. COPPER FROM STEEL FRAMING, STEEL CLAMPS.
12/01/2005 PLUMBING - PROGRESS BBENEDON Approved IVRS - Inspection :* ROOF DRAINS OK
WH DRAIN PANS OK
ENERGY CONSERVATION REQUIREMENTS TO BE MADE BY THE USE OF HEAT TRAP NIPPLES.
RUNNING WATER TEST TO ALL UNDER CONNECTIONS OK. EXCEPT UNIT & 134
RETEST # 134 CALL FOR INSPECTION. PROVIDE TEST ONTUB WASTE & OVER FLOWS ALL UNITS. OK TO COVER ALL WALLS EXCEPT AT REQUIRED TEST LOCATIONS.
12/01/2005 FRAMING AMATHIES Approved IVRS - Inspection :*
12/01/2005 PLUMBING - SEWER HCS CONNECT BBENEDON Approved IVRS - Inspection :*
12/01/2005 PLUMBING - YARD WTR LINE/TEST BBENEDON Approved IVRS - Inspection :*
12/01/2005 PLUMBING - ABOVE CEILING BBENEDON Approved IVRS - Inspection :*
12/02/2005 PLUMBING - INTERMEDIATE BBENEDON Approved IVRS - Inspection :* TUB DRAINS, WASTE & OVERFLOW TEST OK
RUN TEST FOR CONNECTION TO EXISTING @ # 134 OK
CLOSET FLANGES OK
12/13/2005 SHEET ROCK NAILING AMATHIES Approved IVRS - Inspection :*
12/16/2005 STUCCO MESH AMATHIES Approved IVRS - Inspection :*APPROVED
12/28/2005 U VALUE FOR WINDOW LHANLY Approved IVRS - Inspection :*
12/30/2005 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :*
12/30/2005 ELECTRIC - OUTDOOR LIGHTING DSANTACR Approved IVRS - Inspection :*
12/30/2005 TEP CLEARANCE - PM JWEATHER Approved CLEAR RECN FOR UNITS: #133, 134, 144, 145, 333, 334, 343 AND 344
01/06/2006 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :*
01/09/2006 BUILDING - FINAL LHANLY Approved IVRS - Inspection :*
01/10/2006 PERMIT FINALED JWEATHER Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW