Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL NEW
Address:
3400 E GLOBAL LP
Address NEW:
3400 E GLOBAL LP
Apply Date:
04/25/2005
Applicant:
METRO PERMIT EXPRESS
Description:
NEW SHELL (MANUFACTURING)
Architects:
  • MORROW, KEVIN THOMAS

Permit Reviews

Permit Number - T05CM01823
Permit Status: Final
Permit Description: NEW SHELL (MANUFACTURING)
Start Date Submittal Complete Date Status  
04/25/2005 PLANS OK TO SUBMIT - 3RD PARTY 04/26/2005 COMPLETED Review Details
04/26/2005 3RD PARTY REVIEW-COMMERCIAL 06/15/2005 COMPLETED Review Details
06/15/2005 POST 3RD PARTY REVIEW 06/29/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM01823
Permit Status: Final
Permit Description: NEW SHELL (MANUFACTURING)
Total Outstanding Activity Conditions - 1
Date Name
04/25/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T05CM01823
Permit Description: NEW SHELL (MANUFACTURING)
Total Completed Inspections - 25
Date Description Inspector Results Comments
09/12/2005 PLUMBING - ROUGH, SOIL TRINIVJR Approved IVRS - Inspection :*
09/18/2005 PLUMBING - SEWER HCS CONNECT TRINIVJR Approved IVRS - Inspection :*
1) HCS CONNECTION IS OK
2) OK TO BACKFILL TRENCH
10/21/2005 EXCAVATION/LAYOUT REBAR & ZON AMATHIES Approved IVRS - Inspection :*PERIMETER FTGS OK
10/24/2005 ELECTRIC - UFER DSANTACR Approved IVRS - Inspection :*
12/06/2005 ROOF NAILING AMATHIES Approved IVRS - Inspection :*
12/12/2005 ELECTRIC - UNDERGROUND RSUBA Approved IVRS - Inspection :*
4" (2) FOR FUTURE T.I.
12/16/2005 BUILDING PRE-SLAB AMATHIES Approved IVRS - Inspection :*LOT # 13 OK
12/23/2005 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*TWO 2" TYPE K COPPER WATER RISERS WITH SIL.FOS'D 90 DEGREE AND 100# PRESSURE OK
BE SURE AND RECALL INSPECTION WHEN THEY ARE INSTALLED.
01/04/2006 PLUMBING - BACK WATER VALVE BBENEDON Approved IVRS - Inspection :*
01/05/2006 PLUMBING - INTERMEDIATE BBENEDON Approved IVRS - Inspection :*
01/13/2006 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
01/13/2006 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
01/18/2006 SHEET ROCK NAILING LHANLY Approved IVRS - Inspection :*
01/18/2006 U VALUE FOR WINDOW LHANLY Approved IVRS - Inspection :*
01/18/2006 BUILDING ABOVE CEILING LHANLY Approved IVRS - Inspection :*
01/18/2006 EXT METAL CLIPS/EXT SHEATHING LHANLY Approved IVRS - Inspection :*
01/18/2006 FRAMING LHANLY Approved IVRS - Inspection :*
03/29/2006 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :*
03/29/2006 OUTDOOR LIGHTING FINAL DSANTACR Approved IVRS - Inspection :*
03/29/2006 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection :*
03/29/2006 PLUMBING - FINAL BBENEDON Approved IVRS - Inspection :*
04/13/2006 FIRE - FINAL LTHOMAS Approved
04/13/2006 FIRE SPKLR - FINAL LTHOMAS Approved
10/17/2006 ENGINEERING - FINAL MAVERY Approved Complete punch list.
Global Loop
T05CM01823
T01BU03068
1. Have engineer certify basin and drainage wasy per chaper XIV, section 14.2(7).
2. Install trucated domes on all HC ramps.
3. Install wheel stops rear of building.
4. Repair curb around basin.
5. Repair erosion in basin inlets.
6. Close out grading permit T01BU03068.
7. Clear all drain pipes in detention basins.
8. Cut all vegatation in bottom of detention basins.
9. Stabilize all slopes 2 to 1 and steeper.
10. Address erosion starting under parking lot. (eastside basin)
11. Have all changes to westside of project approved at 201 N. Stone.
12. Complete safety barrier around all basins.
01/29/2007 BUILDING - FINAL AALEGRIA Approved IVRS - Inspection :*

Documents

File Name Document Type  
T05CM01823 2025 MASS-UPLOAD.PDF DOCUMENTS VIEW