Permit: T05CM01823

Parcel: 14029022B


Addresses:

3400 E GLOBAL LP

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
01/05/2006 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
01/04/2006 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE WATER TEST ON WATER PIPING - 60 PSI
12/23/2005 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*TWO 2" TYPE K COPPER WATER RISERS WITH SIL.FOS'D 90 DEGREE AND 100# PRESSURE OK
BE SURE AND RECALL INSPECTION WHEN THEY ARE INSTALLED.
09/15/2005 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) 2" C.W. SUPPLY FROM METER AND BACKFLOW PREVENTER LOCATION TO 5' FROM BLDG PAD IS OK
2) AIR PRESSURE TEST IS OK
3) OK TO BACKFILL TRENCH