Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
C of o
Type:
COMMERCIAL ADDITION
Address:
1117 W GRANT RD
Address NEW:
1117 W GRANT RD
Apply Date:
04/13/2005
Applicant:
CAYLOR CONSTRUCTION COMPANY , RO
Description:
ADDITION COMMERCIAL WAREHOUSE
Contractors:
  • CAYLOR CONSTRUCTION COMPANY , RO

Permit Reviews

Permit Number - T05CM01618
Permit Status: C of o
Permit Description: ADDITION COMMERCIAL WAREHOUSE
Start Date Submittal Complete Date Status  
02/21/2006 3RD PARTY REVIEW-REVISION/OTHER 02/21/2006 COMPLETED Review Details
04/13/2005 PLANS OK TO SUBMIT - 3RD PARTY 04/13/2005 COMPLETED Review Details
04/13/2005 3RD PARTY REVIEW-COMMERCIAL 04/25/2005 COMPLETED Review Details
04/25/2005 POST 3RD PARTY REVIEW 08/16/2005 COMPLETED Review Details
12/19/2005 3RD PARTY REVIEW-REVISION/OTHER 12/19/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM01618
Permit Status: C of o
Permit Description: ADDITION COMMERCIAL WAREHOUSE
Total Outstanding Activity Conditions - 1
Date Name
04/13/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T05CM01618
Permit Description: ADDITION COMMERCIAL WAREHOUSE
Total Completed Inspections - 38
Date Description Inspector Results Comments
09/28/2005 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved IVRS - Inspection :*
10/03/2005 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :* EXTEND 4"CLEAN OUT THROUGH BLDG
OK TO COVER
WATER TEST OK
10/06/2005 STEM WALL/RETAINING WALL AQUIROZ Approved IVRS - Inspection :*
10/23/2005 REINFORCED MASONRY PRE-GROUT AQUIROZ Approved IVRS - Inspection :*
10/30/2005 BUILDING PRE-SLAB AQUIROZ Approved IVRS - Inspection :*
11/15/2005 EXT METAL CLIPS/EXT SHEATHING AMATHIES Approved IVRS - Inspection :*APPROVED
11/15/2005 ROOF NAILING AMATHIES Approved IVRS - Inspection :*APPROVED
12/06/2005 FRAMING AQUIROZ Approved IVRS - Inspection :*
12/07/2005 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection :*HAVE 3050 GAS PRESSURE TEST ADDED TO THE PERMIT AND CALL GAS IN SEPARETLY
HORIZONTAL SECTIONS OF ROOF DRAINS TO BE SUPPORTED.
I AM UNABLE TO FIND ON THEPLAN THE PLUMBING YOU INSTALLED ON THE SEPARATION WALL.
12/07/2005 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
12/07/2005 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
12/09/2005 ELECTRIC - INTERMEDIATE CCLEMENS Approved OK TO COVER WALLS, LEAVE PANELS OPEN
12/22/2005 MECHANICAL - PROGRESS JMILITEL Approved IVRS - Inspection :*ALL DUCT WORK EXPSOED IN AIR CONDITIONED SPACE. INSULATION NOT REQUIRED
12/22/2005 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
12/22/2005 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
12/22/2005 PLUMBING - ROOF DRAINS RMYERS Approved IVRS - Inspection :*
1. ROOF DRAIN WATER TEST OK - I WANT TO SEE THE CONNECTION BETWEEN SQUARE AND ROUND PIPE.
2. GAS ISOMETRIC ON SITE PRESSURE TEST OK - NEW GAS ISOLATED FROM EXISTING.
12/22/2005 FIRE - FINAL LTHOMAS Approved
12/22/2005 FIRE SPKLR - FINAL LTHOMAS Approved
12/22/2005 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
12/22/2005 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
12/22/2005 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
12/22/2005 PLUMBING - GAS PRESSURE TEST RMYERS Approved IVRS - Inspection :*
12/23/2005 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
02/06/2006 BUILDING - PROGRESS AQUIROZ Approved IVRS - Inspection :*
02/06/2006 U VALUE FOR WINDOW AQUIROZ Approved IVRS - Inspection :*
02/06/2006 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
02/06/2006 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
02/07/2006 ENGINEERING - FINAL MRUSSO Approved C OF O FOR ENGINEERING APPROVED
02/08/2006 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
OK FOR FINAL C OF O
02/08/2006 OUTDOOR LIGHTING FINAL CCLEMENS Approved IVRS - Inspection :*
02/08/2006 ELECTRIC - OUTDOOR LIGHTING CCLEMENS Approved IVRS - Inspection :*
02/09/2006 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :*
02/09/2006 ELECTRIC - PROGRESS CCLEMENS Approved IVRS - Inspection :*
02/09/2006 ELECTRIC - SERVICE UPGRADE CCLEMENS Approved IVRS - Inspection :*
02/10/2006 TEP CLEARANCE - AM JKOZUCH Approved ECO
02/23/2006 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL
02/24/2006 BUILDING - FINAL LHANLY Approved IVRS - Inspection :*
02/24/2006 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*REVISED PLAN ON SITE
STUB OUT AT DEMISSING WALL OK