Permit: T05CM01618

Parcel: 115160310


Addresses:

1117 W GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
02/09/2006 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
02/08/2006 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The service is not per code.| 210*NEED MIMINUM # 4CU BOND WIRE FOR RACEWAY'S FROM CT CAN TO DISCONNECT'S NEC 250.102 (C) AND NEC 250.66
NEED TO REMOVE BOND WIRE FROM NEUTRALS AT DISCONNECTS ( LEAVE EQUIPMENT GROUNDS) BOND WIRE CAN END AT BUSING NEC 250.6 9A) & (B)
IT APPEARS SERVICE/PANELS HAVE CHANGED FROM PLAN SINGLE LINE?
02/06/2006 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*