Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T05CM01618
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/09/2006 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
02/08/2006 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The service is not per code.| 210*NEED MIMINUM # 4CU BOND WIRE FOR RACEWAY'S FROM CT CAN TO DISCONNECT'S NEC 250.102 (C) AND NEC 250.66 NEED TO REMOVE BOND WIRE FROM NEUTRALS AT DISCONNECTS ( LEAVE EQUIPMENT GROUNDS) BOND WIRE CAN END AT BUSING NEC 250.6 9A) & (B) IT APPEARS SERVICE/PANELS HAVE CHANGED FROM PLAN SINGLE LINE? |
|
02/06/2006 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |