Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address:
2800 E 36TH ST
Apply Date:
01/04/2005
Applicant:
N/A
Description:
SITE/NEW CHURCH BUILDING
Contractors:
  • A P N BUILDERS INC ,

Permit Reviews

Permit Number - T05CM00027
Permit Status: C of o
Permit Description: SITE/NEW CHURCH BUILDING
Start Date Submittal Complete Date Status  
01/04/2005 PLANS OK TO SUBMIT - SITE 01/05/2005 COMPLETED Review Details
01/05/2005 SITE 03/01/2005 COMPLETED Review Details
03/23/2006 PLANS OK TO SUBMIT - 3RD PARTY 03/29/2006 COMPLETED Review Details
03/29/2006 3RD PARTY REVIEW-COMMERCIAL 06/27/2006 COMPLETED Review Details
04/20/2005 RESUBMITTAL - SITE 06/10/2005 COMPLETED Review Details
06/10/2005 RESUBMITTAL - SITE 06/28/2005 COMPLETED Review Details
06/27/2006 POST 3RD PARTY REVIEW 06/28/2006 COMPLETED Review Details
07/11/2005 RESUBMITTAL - SITE 11/17/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM00027
Permit Status: C of o
Permit Description: SITE/NEW CHURCH BUILDING
Total Outstanding Activity Conditions - 1
Date Name
01/04/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T05CM00027
Permit Description: SITE/NEW CHURCH BUILDING
Total Completed Inspections - 44
Date Description Inspector Results Comments
07/21/2006 PLUMBING - ROUGH, SOIL RLEDONNE Approved IVRS - Inspection :*
PLUMBING ROUGH SOIL, OK INSIDE SLAB
08/11/2006 ELECTRIC - UFER DSANTACR Approved IVRS - Inspection :*
08/17/2006 BUILDING PRE-SLAB LHANLY Approved IVRS - Inspection :*
09/05/2006 EXCAVATION/LAYOUT REBAR & ZON AALEGRIA Approved IVRS - Inspection :*
IN COMPLIANCE WITH APPROVED PLANS
SHEET S1 DETAIL FOR F4 3 #5 E. WAY 2'-6" SQ. X 1'0"
09/13/2006 REINFORCED MASONRY PRE-GROUT AALEGRIA Approved IVRS - Inspection :*
FRONT MASONRY WALL AND COLUMNS
10/31/2006 ELECTRIC - CONSTRUCTION POWER DSANTACR Approved IVRS - Inspection :*
1) OK OUTSIDE TEMP POLE ONLY
10/31/2006 PLUMBING - YARD WTR LINE/TEST RLEDONNE Approved IVRS - Inspection :*
11/01/2006 TEP CLEARANCE - AM JWEATHER Approved TEC CLEARED PER D. SANTACRUZ
11/21/2006 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
SUSPENDED ROUGH DUCT
OK TO PROCEED
11/21/2006 FRAMING AALEGRIA Approved IVRS - Inspection :*
EXCEPT KITCHEN (SHEET A-16)
11/21/2006 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection :*
OK WALLS EXCEPT SOUND ROOM
11/28/2006 PLUMBING - INTERMEDIATE RLEDONNE Approved IVRS - Inspection :*
CALL BACK FOR OVERHEAD DO NOT COVER OVERHEAD
12/04/2006 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection :*
OK U.G CONDUIT & POLE BASES FOR PARKING
12/05/2006 STEM WALL/RETAINING WALL AALEGRIA Approved IVRS - Inspection :*
LIGHT POLE IN COMPLIANCE WITH APPROVED PLANS AND SPEC. DETAIL ON SHEET E4
12/22/2006 SHEET ROCK NAILING AALEGRIA Approved IVRS - Inspection :*
12/22/2006 EXT METAL CLIPS/EXT SHEATHING AALEGRIA Approved IVRS - Inspection :*
12/28/2006 PLUMBING - SEWER HCS CONNECT RRICH Approved IVRS - Inspection :*
01/29/2007 MECHANICAL - HOODS JMILITEL Approved IVRS - Inspection :*
PLANS MAY HAVE BEEN APPROVED IN ERROR
MIN. R5 INSULATION IS REQUIRED ON DUCT INSIDE THE BLDG.
R4.2 WAS INSTALLED
FIRE WRAP IS OK ON GREASE DUCT
02/05/2007 PLUMBING - PRE SLAB RLEDONNE Approved IVRS - Inspection :*
02/16/2007 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
ON FINAL I.D FAN COILS, MARK DATA PLATES,
LEAVE OUT TILE UNDER UNITS
DO NOT RUN WIRES THROUGH A SERVICE PANEL
OK FOR CEILING TILES
02/16/2007 BUILDING ABOVE CEILING AALEGRIA Approved IVRS - Inspection :*
02/16/2007 PLUMBING - ABOVE CEILING RLEDONNE Approved IVRS - Inspection :*
03/09/2007 TEP CLEARANCE - PM JWEATHER Approved TEC CLEARANCE SENT PER B. GRANT
03/22/2007 LANDSCAPE - FINAL ACONNOR Approved
03/22/2007 NPPO - FINAL ACONNOR Approved
03/22/2007 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
03/22/2007 ELECTRIC - OUTDOOR LIGHTING DSANTACR Approved IVRS - Inspection :*
03/22/2007 ELECTRIC - CABLE DROP DSANTACR Approved IVRS - Inspection :*
03/22/2007 ELECTRIC - ABOVE CEILING DSANTACR Approved IVRS - Inspection :*
03/22/2007 OUTDOOR LIGHTING FINAL DSANTACR Approved IVRS - Inspection :*
03/22/2007 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :*
03/23/2007 RIGHT OF WAY - FINAL LLOPEZ Approved PER EMAIL
03/23/2007 BUILDING - FINAL AALEGRIA Approved IVRS - Inspection :*
03/23/2007 ELECTRIC - TEMP POWER FOR TEST DSANTACR Approved
03/26/2007 ROOF NAILING AALEGRIA Approved
03/26/2007 U VALUE FOR WINDOW AALEGRIA Approved
04/13/2007 ENGINEERING - FINAL MAVERY Approved Contractor completed punch list.
04/25/2007 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
AIR BALANCE OK
04/26/2007 FIRE SPKLR - UG PIPING FLUSH LLAKEY Approved
04/26/2007 FIRE SPKLR - UG, PIPING, HYDRO LLAKEY Approved
04/26/2007 FIRE - KITCHEN EXH HOOD FINAL LLAKEY Approved
04/26/2007 FIRE - FINAL LLAKEY Approved
04/26/2007 PLUMBING - FINAL RLEDONNE Approved IVRS - Inspection :*
04/30/2007 PERMIT FINALED BFLORES Approved

Documents

File Name Document Type  
BOND RELEASE DOCUMENTS VIEW
T05CM00027.PDF DOCUMENTS VIEW