Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2007 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* PLANS MAY HAVE BEEN APPROVED IN ERROR MIN. R5 INSULATION IS REQUIRED ON DUCT INSIDE THE BLDG. R4.2 WAS INSTALLED FIRE WRAP IS OK ON GREASE DUCT |