Inspection History: MECHANICAL - FINAL

Permit Number - T05CM00027

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/25/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
AIR BALANCE OK
03/22/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. HAVE ELEC. ENGINEER CALCULATE MIN. & MAX. FUSE SIZE FOR FAN COILS 1, 2, 3, & 4
2. I.D FAN COILS ON FRONT SERVICE PANELS
3. TESTED DUCT SMOKE DETECTORS
4. OK TO FILE FOR TEMP C OF O
5. NEED AIR BALANCE REPORT.
03/08/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. NEED TO TEST DUCT SMOKE DETECTORS
2. SCRATCH DATA PLATES WITH THE PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY.
3. NEED AIR BALANCE REPORT.
4. SET A/C FANS TO RUN CONTINUOUSLY DURING OCCUPIED HOURS.
5. PROVIDE ANTI-SLIP MATERIAL AROUND EXHAUST FAN