Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM00027
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE AIR BALANCE OK |
|
03/22/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. HAVE ELEC. ENGINEER CALCULATE MIN. & MAX. FUSE SIZE FOR FAN COILS 1, 2, 3, & 4 2. I.D FAN COILS ON FRONT SERVICE PANELS 3. TESTED DUCT SMOKE DETECTORS 4. OK TO FILE FOR TEMP C OF O 5. NEED AIR BALANCE REPORT. |
|
03/08/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. NEED TO TEST DUCT SMOKE DETECTORS 2. SCRATCH DATA PLATES WITH THE PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. 3. NEED AIR BALANCE REPORT. 4. SET A/C FANS TO RUN CONTINUOUSLY DURING OCCUPIED HOURS. 5. PROVIDE ANTI-SLIP MATERIAL AROUND EXHAUST FAN |