Permit: T04CM04075
Permit Details
Apply Date:
09/09/2004
Applicant:
N/A
Description:
TI:FRATERNITY KITCHEN
Architects:
- FLOREZ, JESUS L.
Contractors:
- AZ BUILDERS AND MAINTENANCE COMPANY INC
Permit Reviews
Permit Number - T04CM04075
Permit Status: Final
Permit Description: TI:FRATERNITY KITCHEN
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/27/2005 | REVISION | 04/28/2005 | COMPLETED |
| 06/30/2005 | REVISION | 07/14/2005 | COMPLETED |
| 07/29/2005 | REVISION | 07/29/2005 | COMPLETED |
| 09/09/2004 | COMMERCIAL TI | 09/16/2004 | COMPLETED |
| 10/15/2004 | REVISION | 10/22/2004 | COMPLETED |
| 10/22/2004 | RESUBMITTAL | 10/29/2004 | COMPLETED |
| 11/19/2004 | RESUBMITTAL | 12/03/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04CM04075
Permit Status: Final
Permit Description: TI:FRATERNITY KITCHEN
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/09/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T04CM04075
Permit Description: TI:FRATERNITY KITCHEN
Total Completed Inspections - 14
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2004 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :*/SUPPORT M/C WITHIN 12" O F BOX2)SUPPORT PVC CONDUIT AS IT ENTERS WALL 3)TIGHTEN LOOSE FITTINGS (ALL) 4)SUPPORT BOXES 5)PLEASE REVISE PLANS FOR CAN FIXTURES 6)PLEASE ADD 02035,02010,02036 TO PERMIT 7)SUPPORT CONDUITS AS PER CODES 8)INSTALL GROUND SCREWS 3/4 OF A TURN WITH CONDOUTOR |
| 09/20/2004 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :*/1)I WILL REQUIRE A DWV ISOMETRIC FOR REPIPE IN KITCHEN. IT APPEARS THAT THERE IS A MIXED COMBINATION WASTE AND VENT, AND CONVENTIONAL PIPING SYSTEM 2)DBL FIXTURE FITTING MAY NOT BE INSTALLED IN THE HORIZONTAL POSITION 3)GAS UNDER SLAB TO BE SLEEVED IN APPROVED MANNER 4)TEMPORARY DRAINS MUST MAINTAIN AIR GAP 5)WILL REQUIRE AN APPROVED KITCHEN EQUIPMENT PLAN |
| 08/15/2005 | SHEET ROCK NAILING | HLEYVA | Approved | |
| 09/01/2005 | MECHANICAL - INTERMEDIATE | CWILLIAM | Approved | |
| 09/01/2005 | MECHANICAL - ABOVE CEILING | CWILLIAM | Approved | |
| 09/01/2005 | MECHANICAL - HOODS | CWILLIAM | Approved | |
| 09/01/2005 | MECHANICAL - FINAL | CWILLIAM | Approved | IVRS - Inspection :* |
| 09/07/2005 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* 1) CORRECTIONS MADE OK 2) OK TO COVER ALL AREAS 3) GAS OK |
| 09/07/2005 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* |
| 09/07/2005 | ELECTRIC - ABOVE CEILING | DSANTACR | Approved | IVRS - Inspection :* |
| 09/07/2005 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection :* |
| 09/08/2005 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* 1) CORRECTION MADE OK 2) OK FOR C OF O PENDING ANY OTHER INSPECTIONS |
| 09/09/2005 | BUILDING - FINAL | AMATHIES | Approved | IVRS - Inspection :* |
| 09/12/2005 | PERMIT FINALED | CFRAKER | Approved |