Permit: T04CM04075

Parcel: 12317252B


Addresses:

1510 N VINE AV


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T04CM04075

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/01/2005 MECHANICAL - INTERMEDIATE Approved
08/16/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/08/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) LAS WRAP NOT UP AGAINST MASONRY WALL, NORTH SIDE CANNOT WRAP UNDER 1 1/2" CONDUIT. THIS IS A RATED CHASE AND CONNOT ENCOMPASS ANY UTILITY LINES-CONDUITS, ETC... WITHIN THE WRAP
08/02/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) APPROVED DRAWING DETAIL #106-OK. OK TO FIRE WRAP GREASE DUCT
2) DETAIL 102-FULL RADIUS 90 DEGREE ? OVER PARAPET WALL IS INDICATED
3) PARTIAL EAST ELEVATION SPEC. ALL EXPOSED 16 GA. IRON DUCT TO BE PAINTED
4) PROVIDE APPROVED GAS HEATED MATERIAL ABOVE GREASE CATCH RECEPTACLE AS NECESSARY
06/23/2005 MECHANICAL - INTERMEDIATE Cancelled IVRS - RI canceled
06/23/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :* HORIZONTAL SECTION, 16 GA EXH. DUCT, NOT CORRECTLY PITCHED, NOT AS PER APPROVED PLAN.
06/21/2005 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999$ NEED TO CALL ME SO WE CAN DISCUSS HORIZONTAL GREASE DUCT AS INST. DUCT IS NOT MAINTAINING PITCH FROM MASONRY WALL BACK TO HOOD. GREASE WILL COLLECT IN LOWER PART OF DUCT BETWEEN HOOD & 90 DEGREE VERTICLE CHANGE OF DIRECTION. NOT CLEARED TO PROCEED.