Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T04CM04075
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2005 | MECHANICAL - INTERMEDIATE | Approved | ||
| 08/16/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/08/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) LAS WRAP NOT UP AGAINST MASONRY WALL, NORTH SIDE CANNOT WRAP UNDER 1 1/2" CONDUIT. THIS IS A RATED CHASE AND CONNOT ENCOMPASS ANY UTILITY LINES-CONDUITS, ETC... WITHIN THE WRAP |
|
| 08/02/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) APPROVED DRAWING DETAIL #106-OK. OK TO FIRE WRAP GREASE DUCT 2) DETAIL 102-FULL RADIUS 90 DEGREE ? OVER PARAPET WALL IS INDICATED 3) PARTIAL EAST ELEVATION SPEC. ALL EXPOSED 16 GA. IRON DUCT TO BE PAINTED 4) PROVIDE APPROVED GAS HEATED MATERIAL ABOVE GREASE CATCH RECEPTACLE AS NECESSARY |
|
| 06/23/2005 | MECHANICAL - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
| 06/23/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* HORIZONTAL SECTION, 16 GA EXH. DUCT, NOT CORRECTLY PITCHED, NOT AS PER APPROVED PLAN. | |
| 06/21/2005 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999$ NEED TO CALL ME SO WE CAN DISCUSS HORIZONTAL GREASE DUCT AS INST. DUCT IS NOT MAINTAINING PITCH FROM MASONRY WALL BACK TO HOOD. GREASE WILL COLLECT IN LOWER PART OF DUCT BETWEEN HOOD & 90 DEGREE VERTICLE CHANGE OF DIRECTION. NOT CLEARED TO PROCEED. |