Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL OTHER
Apply Date:
03/03/2004
Applicant:
KIM KIRSCHNER
Description:
TI:ART STUDIO
Contractors:
  • KLINE HOMES INC , JOHN W

Permit Reviews

Permit Number - T04CM01012
Permit Status: C of o
Permit Description: TI:ART STUDIO
Start Date Submittal Complete Date Status  
03/03/2004 PLANS OK TO SUBMIT - COMM 03/08/2004 COMPLETED Review Details
03/08/2004 SITE 03/18/2004 COMPLETED Review Details
03/24/2004 RESUBMITTAL - SITE 05/10/2004 COMPLETED Review Details
03/25/2004 3RD PARTY REVIEW-COMMERCIAL TI 05/17/2004 COMPLETED Review Details
05/13/2004 RESUBMITTAL - SITE 05/24/2004 COMPLETED Review Details
05/17/2004 POST 3RD PARTY REVIEW 05/24/2004 COMPLETED Review Details
08/12/2004 3RD PARTY REVIEW-REVISION/OTHER 08/12/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04CM01012
Permit Status: C of o
Permit Description: TI:ART STUDIO
Total Outstanding Activity Conditions - 1
Date Name
03/03/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T04CM01012
Permit Description: TI:ART STUDIO
Total Completed Inspections - 30
Date Description Inspector Results Comments
06/02/2004 PLUMBING - GAS PRESSURE TEST RMYERS Approved IVRS - Inspection :*
06/02/2004 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*/ 1) PVC DWV UNDERGROUND OK. CORRECTIONS MADE OK. 2) OK TO BACKFILL.
07/19/2004 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :*
07/20/2004 ELECTRIC - INTERMEDIATE JORTA Approved IVRS - Inspection :*APPROVED. WALK AND HARD CEILINGS INTERMEDIATE(?).
07/22/2004 PLUMBING - INTERMEDIATE JSTANLEY Approved IVRS - Inspection :*
07/27/2004 ELECTRIC - CABLE DROP MCAPISTR Approved 1. JUMPER FROM BUILDING STEEL TO SPRINKLER PIPE NEC 250-94 2. RE-ROUTE UFER THROUGH EQUIPMENT GROUNDING LUG AT REAR BOTTOM OF C.T. SCAN. DO NOT CUT OR SPLICE UFER TO NEUTRAL USE EMPTY LUG
07/27/2004 ELECTRIC - UFER MCAPISTR Approved IVRS - Inspection :*
08/02/2004 PLUMBING - SEWER HCS CONNECT RRICH Approved IVRS - Inspection :*/ 1) 4" PVC SCHEDULE 40 DWV FROM BLDG 2-WAY CLEANOUT TO HCS CONNECITON WATER TEST APPROVED 2) 2" PVC SCHEDULE 40 AND T/L COPPER FORM METER THRU R.P. BACKFLOW DEVICE TO AND THRU BLDG SERVICE CONNECTION WATER TEST APPROVED 3) WILL NEED CERTIFICATION OF BACKFLOW DEVICE FOR FINAL
08/02/2004 PLUMBING - YARD WTR LINE/TEST RRICH Approved IVRS - Inspection :*
08/05/2004 ELECTRIC - TEMP POWER FOR TEST MCAPISTR Approved IVRS - Inspection :* NO BOND REQUIRED THIS HAD EXISTING POWER AND SERVICE WAS UPGRADED. RTM OK TO CLEAR FOR METER SET.
08/06/2004 TEP CLEARANCE - AM JKOZUCH Approved ECO
08/09/2004 TEP CLEARANCE - PM JKOZUCH Approved PER DELMA ROBEY VIA E-MAIL
08/24/2004 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
08/24/2004 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
08/24/2004 FRAMING AQUIROZ Approved IVRS - Inspection :*
08/26/2004 RIGHT OF WAY - FINAL MOTERO Approved
08/26/2004 ELECTRIC - ABOVE CEILING MCAPISTR Approved IVRS - Inspection :*
08/27/2004 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*/APP
1)HANGERS ADDED AS REQ'D
2) OK TO COVER ALL AREAS
08/27/2004 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection :*
08/27/2004 BUILDING PRE-SLAB AQUIROZ Approved IVRS - Inspection :*
08/27/2004 PLUMBING - GAS PRESS TEST FNL RMYERS Approved IVRS - Inspection :*
08/30/2004 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*/ 1) PLUMBING FINAL OK 2) OK FOR C OF O PENDING ANY OTHER INSPECTIONS
09/07/2004 ELECTRIC - FINAL MCAPISTR Approved IVRS - Inspection :*
09/07/2004 FIRE SPKLR - FINAL CSCHULTZ Approved 1) OK C OF O
09/07/2004 ENGINEERING - FINAL JSALINE Approved C OF O APPROVED.
09/07/2004 FIRE - FINAL CSCHULTZ Approved
09/07/2004 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
09/09/2004 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :*
09/10/2004 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
09/13/2004 PERMIT FINALED JWEATHER Approved

Documents

File Name Document Type  
C OF O_09-13-2004.TIF CERT OF OCC VIEW
None DOCUMENTS VIEW