Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T04CM01012
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2004 | ELECTRIC - CABLE DROP | Approved | 1. JUMPER FROM BUILDING STEEL TO SPRINKLER PIPE NEC 250-94 2. RE-ROUTE UFER THROUGH EQUIPMENT GROUNDING LUG AT REAR BOTTOM OF C.T. SCAN. DO NOT CUT OR SPLICE UFER TO NEUTRAL USE EMPTY LUG |