Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04CM01012

Parcel: 111073140

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T04CM01012

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
07/27/2004 ELECTRIC - CABLE DROP Approved 1. JUMPER FROM BUILDING STEEL TO SPRINKLER PIPE NEC 250-94 2. RE-ROUTE UFER THROUGH EQUIPMENT GROUNDING LUG AT REAR BOTTOM OF C.T. SCAN. DO NOT CUT OR SPLICE UFER TO NEUTRAL USE EMPTY LUG