Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM01012
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/20/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :*APPROVED. WALK AND HARD CEILINGS INTERMEDIATE(?). | |
07/19/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :TIGHTEN LOOSE FITTINGS SUPPORT M/C CABLE AT 6' ON THE HORIZONTAL RUNS PROTECT M/C IN CHANEL WITH LESS THAN 1 1/4" FROM EDGE PREVENT DIRECT ELECTRICAL CONTACT |
|
06/17/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ PARTIAL OK FOR NORTH WALL AND EAST WALL. NOTE: THE SWITCH FOR RECEPTACLES UNDER KEY NOTE 5 ON SHEET E-2 NOT PIPED IN. UNDERGROUND NOT INSPECTED? |