Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address NEW:
8800 E TANQUE VERDE RD
Apply Date:
01/12/2004
Applicant:
LESLIE'S POOL
Description:
TI:POOL COMPANY
Contractors:
  • INTEGRATED CONSTRUCTION CORP ,

Permit Reviews

Permit Number - T04CM00104
Permit Status: C of o
Permit Description: TI:POOL COMPANY
Start Date Submittal Complete Date Status  
01/12/2004 COMMERCIAL TI 01/15/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04CM00104
Permit Status: C of o
Permit Description: TI:POOL COMPANY
Total Outstanding Activity Conditions - 1
Date Name
01/12/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T04CM00104
Permit Description: TI:POOL COMPANY
Total Completed Inspections - 21
Date Description Inspector Results Comments
02/17/2004 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection 0000*/ 1) OK WALLS
02/17/2004 FRAMING RSUBA Approved IVRS - Inspection 0000*
02/20/2004 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection 0000*/ H2O IN WALL PRESSURE TEST OK. OK TO COVER. ABOVE CEILING VENTS TO HAVE APPROVED HANGERS. ABOVE CEILING H2O PIPING TO HAVE APPROVED HANGERS. WILL NEED TO SEE CLOSET FLANGES PRIOR TO SETTING OF STOOLS.
02/20/2004 PLUMBING - ROUGH, SOIL RRICH Approved IVRS - Inspection 0000*/ WATRE TEST WASTE AND VENT UNDERSLAB UP TO CONNECTION TO EXISTING 2" VENT THRU ROOF APPROVED. CLOSET DEMO STUB 3" AND 4" TO BE GLUE STYLE PERM CAP. OK TO COVER. ALL DEMOED FIXTURES TO HAVE GLUE STYLE PERM CAPS.
02/23/2004 SHEET ROCK NAILING HLEYVA Approved IVRS - Inspection 0000*
02/24/2004 PLUMBING - PROGRESS RRICH Approved IVRS - Inspection 0000*/ 1) CLOSET FLING OK, DEMO PLUMBING CAPPED BELOW FLOOR
03/05/2004 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection 0000*/ 1) NEED TO SEE FIRE DAMPER OPENINGS IN WALL PRIOR TO INSTALLING DAMPERS. 2) DUCT SMOKE DETECTORS TO BE INSTALLED IN THE RETURN DUCTS AS PER 2000 IMC. 3) CONDESATE DRAINS CANNOT TERMINATE DIRECTLY INTO A SEWER VENT. DISCUSSED ALTERNATE METHOD WITH CONTRACTOR. OK FOR CEILING TILES. LEAVE OUT UNDER EACH DUCT SMOKE DETECTOR.
03/05/2004 PLUMBING - ABOVE CEILING JSTANLEY Approved IVRS - Inspection 0000*
03/09/2004 MECHANICAL - PROGRESS JMILITEL Approved IVRS - Inspection 0000*/ INSPECTED SMOKE DETECTORS, FIRE DAMPER OPENINGS. ADD MORE BLOCKING UNDER CONDENSATE DRAIN LINE AND CLAMP TO BLOCKS.
03/09/2004 PLUMBING - FINAL RRICH Approved IVRS - Inspection 0000*
03/10/2004 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection 0000*/ 1) OK FOR FINAL C OF O
03/10/2004 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection 0000*/ OK FINAL. A DISCONNECTING MEANS IS NEEDED FOR WEST HOT.
03/10/2004 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection 0000*
03/10/2004 BUILDING - FINAL RSUBA Approved IVRS - Inspection 0000*
03/10/2004 BUILDING ABOVE CEILING RSUBA Approved IVRS - Inspection 0000*
03/11/2004 FIRE - FINAL CSCHULTZ Approved
03/11/2004 FIRE SPKLR - FINAL CSCHULTZ Approved
03/15/2004 PERMIT FINALED JYBARRA Approved
03/15/2004 RIGHT OF WAY - FINAL PWHIDDON Approved
03/15/2004 SIGN - FINAL JYBARRA Approved IVRS - Inspection 0000*
03/15/2004 ENGINEERING - FINAL JSALINE Approved C OF O APPROVED.

Documents

File Name Document Type  
None DOCUMENTS VIEW
C OF O_03-16-2004.TIF CERT OF OCC VIEW