Permit: T04CM00104
Permit Details
Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
8800 E TANQUE VERDE RD
Address NEW:
8800 E TANQUE VERDE RD
Apply Date:
01/12/2004
Applicant:
LESLIE'S POOL
Description:
TI:POOL COMPANY
Contractors:
- INTEGRATED CONSTRUCTION CORP ,
Permit Reviews
Permit Number - T04CM00104
Permit Status: C of o
Permit Description: TI:POOL COMPANY
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/12/2004 | COMMERCIAL TI | 01/15/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04CM00104
Permit Status: C of o
Permit Description: TI:POOL COMPANY
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/12/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T04CM00104
Permit Description: TI:POOL COMPANY
Total Completed Inspections - 21
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/17/2004 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection 0000*/ 1) OK WALLS |
| 02/17/2004 | FRAMING | RSUBA | Approved | IVRS - Inspection 0000* |
| 02/20/2004 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection 0000*/ H2O IN WALL PRESSURE TEST OK. OK TO COVER. ABOVE CEILING VENTS TO HAVE APPROVED HANGERS. ABOVE CEILING H2O PIPING TO HAVE APPROVED HANGERS. WILL NEED TO SEE CLOSET FLANGES PRIOR TO SETTING OF STOOLS. |
| 02/20/2004 | PLUMBING - ROUGH, SOIL | RRICH | Approved | IVRS - Inspection 0000*/ WATRE TEST WASTE AND VENT UNDERSLAB UP TO CONNECTION TO EXISTING 2" VENT THRU ROOF APPROVED. CLOSET DEMO STUB 3" AND 4" TO BE GLUE STYLE PERM CAP. OK TO COVER. ALL DEMOED FIXTURES TO HAVE GLUE STYLE PERM CAPS. |
| 02/23/2004 | SHEET ROCK NAILING | HLEYVA | Approved | IVRS - Inspection 0000* |
| 02/24/2004 | PLUMBING - PROGRESS | RRICH | Approved | IVRS - Inspection 0000*/ 1) CLOSET FLING OK, DEMO PLUMBING CAPPED BELOW FLOOR |
| 03/05/2004 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection 0000*/ 1) NEED TO SEE FIRE DAMPER OPENINGS IN WALL PRIOR TO INSTALLING DAMPERS. 2) DUCT SMOKE DETECTORS TO BE INSTALLED IN THE RETURN DUCTS AS PER 2000 IMC. 3) CONDESATE DRAINS CANNOT TERMINATE DIRECTLY INTO A SEWER VENT. DISCUSSED ALTERNATE METHOD WITH CONTRACTOR. OK FOR CEILING TILES. LEAVE OUT UNDER EACH DUCT SMOKE DETECTOR. |
| 03/05/2004 | PLUMBING - ABOVE CEILING | JSTANLEY | Approved | IVRS - Inspection 0000* |
| 03/09/2004 | MECHANICAL - PROGRESS | JMILITEL | Approved | IVRS - Inspection 0000*/ INSPECTED SMOKE DETECTORS, FIRE DAMPER OPENINGS. ADD MORE BLOCKING UNDER CONDENSATE DRAIN LINE AND CLAMP TO BLOCKS. |
| 03/09/2004 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection 0000* |
| 03/10/2004 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection 0000*/ 1) OK FOR FINAL C OF O |
| 03/10/2004 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection 0000*/ OK FINAL. A DISCONNECTING MEANS IS NEEDED FOR WEST HOT. |
| 03/10/2004 | ELECTRIC - ABOVE CEILING | RHOLLAND | Approved | IVRS - Inspection 0000* |
| 03/10/2004 | BUILDING - FINAL | RSUBA | Approved | IVRS - Inspection 0000* |
| 03/10/2004 | BUILDING ABOVE CEILING | RSUBA | Approved | IVRS - Inspection 0000* |
| 03/11/2004 | FIRE - FINAL | CSCHULTZ | Approved | |
| 03/11/2004 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | |
| 03/15/2004 | PERMIT FINALED | JYBARRA | Approved | |
| 03/15/2004 | RIGHT OF WAY - FINAL | PWHIDDON | Approved | |
| 03/15/2004 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection 0000* |
| 03/15/2004 | ENGINEERING - FINAL | JSALINE | Approved | C OF O APPROVED. |