Permit: T04CM00104

Parcel: 114540650

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/05/2004 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*/ 1) NEED TO SEE FIRE DAMPER OPENINGS IN WALL PRIOR TO INSTALLING DAMPERS. 2) DUCT SMOKE DETECTORS TO BE INSTALLED IN THE RETURN DUCTS AS PER 2000 IMC. 3) CONDESATE DRAINS CANNOT TERMINATE DIRECTLY INTO A SEWER VENT. DISCUSSED ALTERNATE METHOD WITH CONTRACTOR. OK FOR CEILING TILES. LEAVE OUT UNDER EACH DUCT SMOKE DETECTOR.