Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2004 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*/ 1) NEED TO SEE FIRE DAMPER OPENINGS IN WALL PRIOR TO INSTALLING DAMPERS. 2) DUCT SMOKE DETECTORS TO BE INSTALLED IN THE RETURN DUCTS AS PER 2000 IMC. 3) CONDESATE DRAINS CANNOT TERMINATE DIRECTLY INTO A SEWER VENT. DISCUSSED ALTERNATE METHOD WITH CONTRACTOR. OK FOR CEILING TILES. LEAVE OUT UNDER EACH DUCT SMOKE DETECTOR. |