Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Final
Type:
COMMERCIAL NEW
Address NEW:
6330 E GOLF LINKS RD
Apply Date:
12/29/2003
Applicant:
N/A
Description:
SHELL BLDG
Architects:
  • PASHKOWSKI, GEOFFREY LYNN
Contractors:
  • GRACE CONTRACTORS INC

Permit Reviews

Permit Number - T03CM05891
Permit Status: Final
Permit Description: SHELL BLDG
Start Date Submittal Complete Date Status  
02/13/2004 RESUBMITTAL - SITE 03/22/2004 COMPLETED Review Details
02/13/2004 3RD PARTY REVIEW-COMMERCIAL 02/23/2004 COMPLETED Review Details
03/22/2004 RESUBMITTAL - SITE 04/14/2004 COMPLETED Review Details
04/20/2004 3RD PARTY REVIEW-COMMERCIAL 04/20/2004 COMPLETED Review Details
04/22/2004 POST 3RD PARTY REVIEW 05/06/2004 COMPLETED Review Details
09/17/2004 3RD PARTY REVIEW-REVISION/OTHER 09/27/2004 COMPLETED Review Details
10/26/2004 3RD PARTY REVIEW-REVISION/OTHER 10/29/2004 COMPLETED Review Details
12/29/2003 PLANS OK TO SUBMIT - 3RD PARTY 12/29/2003 COMPLETED Review Details
12/29/2003 SITE 02/13/2004 COMPLETED Review Details
12/31/2003 3RD PARTY REVIEW-COMMERCIAL 01/16/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T03CM05891
Permit Status: Final
Permit Description: SHELL BLDG
Total Outstanding Activity Conditions - 1
Date Name
12/29/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T03CM05891
Permit Description: SHELL BLDG
Total Completed Inspections - 35
Date Description Inspector Results Comments
06/08/2004 ELECTRIC - UFER JORTA Approved IVRS - Inspection :*
06/15/2004 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved IVRS - Inspection :*/ 1) PER RFI SK2
06/23/2004 PLUMBING - ROUGH, SOIL RRICH Approved IVRS - Inspection :*/ CORRECTIONS MADE WTR TEST OK UNDERGROUND.
07/06/2004 BUILDING PRE-SLAB LHANLY Approved IVRS - Inspection :*
08/20/2004 REINFORCED MASONRY PRE-GROUT LHANLY Approved IVRS - Inspection :*
09/07/2004 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*/ 1) INSPECTED SUPPLY AND EXHAUST IN RESTROOMS 2) INSPECTED CONDENSATE DRAIN LINES 3) OK FOR SHEET ROCK
09/07/2004 ROOF NAILING LHANLY Approved IVRS - Inspection :*
09/21/2004 FRAMING LHANLY Approved IVRS - Inspection :*APPROVED.
09/21/2004 STEM WALL/RETAINING WALL LHANLY Approved IVRS - Inspection :*APPROVED.
09/23/2004 SHEET ROCK NAILING LHANLY Approved IVRS - Inspection :*
09/28/2004 STUCCO MESH LHANLY Approved IVRS - Inspection :*
09/28/2004 PLUMBING - ROOF DRAINS RRICH Approved SUITE #1 CLOSET FLANGE OK. 03037 ROOF DRAINS APPROVED PER REVISED CITY APPROVED PLANS
09/29/2004 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection :*
09/29/2004 PLUMBING - ABOVE CEILING RRICH Approved IVRS - Inspection :*
09/30/2004 ELECTRIC - INTERMEDIATE JORTA Approved IVRS - Inspection :*WALK APPROVED. COMPLETE. *NOTE* ABOVE CEILING AT SUITE 1 NOT APPROVED-IN VIOLATION OF 110.26. FIRE SPRINKLER PIPE IN DEDICATED SPACE AT THE TOP OF PANEL BOARD.
10/06/2004 BUILDING ABOVE CEILING LHANLY Approved IVRS - Inspection :*
10/07/2004 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*/DO NOT REDUCE CONDENSATE CONNECTION TO LAV. TAILPIECE. NEED TO SEE DUCT SMOKE DETECTORS WIRED. LEAVE OUT A CEILING TILE UNDER EACH DETECTOR . WILL CHECK ON FINAL.
10/19/2004 ELECTRIC - ABOVE CEILING JORTA Approved
10/21/2004 PLUMBING - SEWER HCS CONNECT RRICH Approved IVRS - Inspection :*
10/26/2004 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*/OK FOR FINAL
11/03/2004 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*/1)COPY OF BACKFLOW CERTIFICATION
11/05/2004 OUTDOOR LIGHTING FINAL JORTA Approved
11/12/2004 U VALUE FOR WINDOW LHANLY Approved IVRS - Inspection :*
11/22/2004 TEP CLEARANCE - PM JKOZUCH Approved ECO HOUSE PANEL PER RANDY SCHULER'S E-MAIL
11/24/2004 LANDSCAPE - FINAL ACONNOR Approved
11/29/2004 ELECTRIC - FINAL RSUBA Approved IVRS - Inspection :*/ 1) SUBJECT TO LETTER
11/29/2004 ELECTRIC - CABLE DROP RSUBA Approved IVRS - Inspection :*
11/29/2004 FIRE - FINAL LTHOMAS Approved
11/29/2004 FIRE SPKLR - FINAL LTHOMAS Approved
11/29/2004 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
11/29/2004 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
11/29/2004 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
11/30/2004 PERMIT FINALED BGRANT Approved
11/30/2004 ELECTRIC - UNDERGROUND JORTA Approved
11/30/2004 BUILDING - FINAL LHANLY Approved IVRS - Inspection :*