Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T03CM05891
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2004 | ELECTRIC - ABOVE CEILING | Approved | ||
10/11/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
10/08/2004 | ELECTRIC - ABOVE CEILING | Denied | M.C.CABLE NEEDS PROPER INDEPENDANT SUPPORT IF LONGER THAN 6' | |
10/06/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) FIRE SPRINKLER PIPING NOT TO BE IN THE DEDICATED SPACE ABOVE THE INTERIOR PANEL BOARD, ANYTHING (FORIEGN PIPING) ABOVE 6' AREA STILL REQUIRES SOME TYPE OF DIVERSION FROM LEAKING SUBSTANCES |