Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T03CM04797
Permit Details
Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
8240 E 22ND ST #115
Address NEW:
8240 E 22ND ST #115
Apply Date:
10/06/2003
Applicant:
INTERTECH
Description:
TI:AUTOGLASS STORE
Architects:
- SWAN WAYNE E
Contractors:
- PROGRESSIVE STRUCTURES
Permit Reviews
Permit Number - T03CM04797
Permit Status: C of o
Permit Description: TI:AUTOGLASS STORE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/06/2003 | COMMERCIAL TI | 10/08/2003 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T03CM04797
Permit Status: C of o
Permit Description: TI:AUTOGLASS STORE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/06/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T03CM04797
Permit Description: TI:AUTOGLASS STORE
Total Completed Inspections - 16
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2003 | MECHANICAL - PROGRESS | JMILITEL | Approved | IVRS - Inspection 0000* |
| 10/30/2003 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection 0000* |
| 10/30/2003 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection 0000* |
| 10/30/2003 | ELECTRIC - FINAL | JORTA | Approved | IVRS - Inspection 0000*/ OPEN WALLS WHERE INDICATED ON PLAN. 12" EACH WAY FROM CONDUIT. TOTAL 24" WIDE - 3 AREAS - SEE PLAN. OPEN ALL BOXES FOR INSPECTION OF MAKE UP. PLEASE RECALL INTERMEDIATE. BOX THAT IS NOW EXPOSED AT REAR IS OVERFILLED WITH CONDUCTORS. |
| 10/30/2003 | ELECTRIC - INTERMEDIATE | JORTA | Approved | IVRS - Inspection 0000* |
| 10/30/2003 | BUILDING ABOVE CEILING | AMATHIES | Approved | IVRS - Inspection 0000* |
| 10/30/2003 | FRAMING | AMATHIES | Approved | IVRS - Inspection 0000* |
| 10/31/2003 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection 0999*/ 1) A/C UNIT OVERFUSED 25 AMP IS MAX FUSE SIZE 2) MARK DATA PLATE WITH PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY. IDENTIFY FUSE BANKS IN DISCONNECTS. 3) PROVIDE A FRESH AIR INTAKE AS PER PLANS 4) CONDENSATE CANNOT TERMINATE INTO A HOLE DRILLED INTO THE SIE OF A SEWER VENT. TERMINATE TO LAV TAIL PIECE AS PER PLANS. ALSO CONENCT EXISTING UNIT TO SAME DRAIN LINE 5) PERMANENTLY LABEL A/C UNIT WITH SUITE NUMBER. RECALL FOR INSPECTION |
| 11/07/2003 | SHEET ROCK NAILING | LHANLY | Approved | IVRS - Inspection 0000*/ CANCELLED BY CONTRACTOR. |
| 12/02/2003 | ELECTRIC - ABOVE CEILING | JORTA | Approved | IVRS - Inspection 0000*/ PLEASE COMPLY WITH LAST INSP. - NEED L11 NAME, GEN. CONTRACTOR NAME AND TELE. NUMBER. RECALL AND LEAVE NAME AND #. |
| 03/04/2004 | PERMIT FINALED | DLEE | Approved | |
| 03/04/2004 | RIGHT OF WAY - FINAL | DLEE | Approved | |
| 03/04/2004 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection 0000* |
| 03/04/2004 | ENGINEERING - FINAL | JSALINE | Approved | C OF O APPROVED. |
| 03/04/2004 | FIRE - FINAL | LTHOMAS | Approved | 1) OK C OF O |
| 03/10/2004 | BUILDING - FINAL | LHANLY | Approved | IVRS - Inspection 0000* |