Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/10/2004 |
SHEET ROCK NAILING |
|
Approved |
IVRS - Inspection 0000* |
| 03/04/2004 |
SHEET ROCK NAILING |
|
Denied |
IVRS - Inspection 0999* 2 HOUR PENETRATION DOES NOT EXTENDD TO DECK ON WEST SIDE .2) 2 HOUR PARTION DOES NOT COMPLY WITH DETAIL 10/A2. 3) THERE ARE SEVERAL OPEN PENETRATIONS IN 2 HOUR PARTION ON WEST SIDE. |
| 11/07/2003 |
SHEET ROCK NAILING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ CANCELLED BY CONTRACTOR. |
| 11/04/2003 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* EST ROOM OK TO TAPE i STILL NEED TO SEE ABOVE CEILING ON OFFICE SIDE |