Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/02/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ OK FOR FINAL |
| 02/20/2004 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ INSPECTION CANCELLED |
| 02/19/2004 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 02/13/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 01/30/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ CONDENSATE TERMINATION NOT TO CODE OR PER APPROVED PLAN. |
| 10/31/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) A/C UNIT OVERFUSED 25 AMP IS MAX FUSE SIZE 2) MARK DATA PLATE WITH PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY. IDENTIFY FUSE BANKS IN DISCONNECTS. 3) PROVIDE A FRESH AIR INTAKE AS PER PLANS 4) CONDENSATE CANNOT TERMINATE INTO A HOLE DRILLED INTO THE SIE OF A SEWER VENT. TERMINATE TO LAV TAIL PIECE AS PER PLANS. ALSO CONENCT EXISTING UNIT TO SAME DRAIN LINE 5) PERMANENTLY LABEL A/C UNIT WITH SUITE NUMBER. RECALL FOR INSPECTION |
| 10/30/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ NEED ACCESS TO ROOF. |