Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM04797
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ OK FOR FINAL | |
02/20/2004 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ INSPECTION CANCELLED | |
02/19/2004 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
02/13/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* | |
01/30/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ CONDENSATE TERMINATION NOT TO CODE OR PER APPROVED PLAN. | |
10/31/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) A/C UNIT OVERFUSED 25 AMP IS MAX FUSE SIZE 2) MARK DATA PLATE WITH PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY. IDENTIFY FUSE BANKS IN DISCONNECTS. 3) PROVIDE A FRESH AIR INTAKE AS PER PLANS 4) CONDENSATE CANNOT TERMINATE INTO A HOLE DRILLED INTO THE SIE OF A SEWER VENT. TERMINATE TO LAV TAIL PIECE AS PER PLANS. ALSO CONENCT EXISTING UNIT TO SAME DRAIN LINE 5) PERMANENTLY LABEL A/C UNIT WITH SUITE NUMBER. RECALL FOR INSPECTION | |
10/30/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ NEED ACCESS TO ROOF. |