Permit Details

Status:
C of o
Type:
COMMERCIAL ADDITION
Address NEW:
1695 N COUNTRY CLUB RD
Apply Date:
04/16/2003
Applicant:
N/A
Description:
ADDITION:PHYSICAL EDUCATION BLDG & EXPAND:KITCHEN
Architects:
  • TOM, RICHARD FE
Contractors:
  • CORONA SIERRA INC ,
  • TUCSON UNIFIED SCHOOL DIST #1

Permit Reviews

Permit Number - T03CM01875
Permit Status: C of o
Permit Description: ADDITION:PHYSICAL EDUCATION BLDG & EXPAND:KITCHEN
Start Date Submittal Complete Date Status  
01/12/2005 RESUBMITTAL 01/21/2005 COMPLETED Review Details
04/06/2004 PLANS OK TO SUBMIT - SITE 10/14/2004 COMPLETED Review Details
04/16/2003 PLANS OK TO SUBMIT - COMM 05/08/2003 COMPLETED Review Details
05/08/2003 COMMERCIAL NEW 06/12/2003 COMPLETED Review Details
07/29/2005 REVISION 07/29/2005 COMPLETED Review Details
09/26/2003 RESUBMITTAL 12/08/2003 COMPLETED Review Details
10/14/2004 RESUBMITTAL 11/24/2004 COMPLETED Review Details
10/26/2005 REVISION 10/26/2005 COMPLETED Review Details
10/26/2005 REVISION 12/06/2005 COMPLETED Review Details
11/24/2004 RESUBMITTAL - SITE 01/04/2005 COMPLETED Review Details
11/24/2004 RESUBMITTAL 01/04/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T03CM01875
Permit Status: C of o
Permit Description: ADDITION:PHYSICAL EDUCATION BLDG & EXPAND:KITCHEN
Total Outstanding Activity Conditions - 1
Date Name
04/16/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T03CM01875
Permit Description: ADDITION:PHYSICAL EDUCATION BLDG & EXPAND:KITCHEN
Total Completed Inspections - 35
Date Description Inspector Results Comments
01/28/2005 ELECTRIC - UFER RMAJUTA Approved IVRS - Inspection :* APPROVED. 20' OF #4 BARE COPPER TO BOTTOM REBAR
02/04/2005 STEM WALL/RETAINING WALL BSTEVENS Approved IVRS - Inspection :* APPROVED
02/16/2005 PLUMBING - ROUGH, SOIL TRINIVJR Approved IVRS - Inspection :* 1) SOIL WATER TEST IS OK. 2) BLDG DRAIN IS STUBBED OUT @ 2' OF FOOTER ONLY. 3) OK TO BACKFILL TRENCH. 4) NOTE: SHALL RED LINE APPROVED DRAWING SHOWING OPPOSITE EXIT OF BLDG DRAIN
03/07/2005 BUILDING PRE-SLAB AQUIROZ Approved IVRS - Inspection :* APPROVED
03/25/2005 ELECTRIC - UNDERGROUND RMAJUTA Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) NO UNDERGROUND TO INSPECT
06/27/2005 ROOF NAILING AQUIROZ Approved IVRS - Inspection :*
07/01/2005 ELECTRIC - INTERMEDIATE MCAPISTR Approved IVRS - Inspection :*
1) ROUGH-IN IN PROGRESS
07/19/2005 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
07/27/2005 STUCCO MESH AQUIROZ Approved IVRS - Inspection :*
09/20/2005 PLUMBING - INTERMEDIATE TRINIVJR Approved IVRS - Inspection :*
1) DWV WATER TEST IS OK
2) OVERHEAD WATER DISTRIBUTION IS OK
3) OK FOR DRY WALL
09/20/2005 PLUMBING - ABOVE CEILING TRINIVJR Approved IVRS - Inspection :*
09/21/2005 PLUMBING - SEWER HCS CONNECT TRINIVJR Approved IVRS - Inspection :*
1) SOIL WATER TEST IS OK
2) HCS CONNECTION IS OK
3) OK TO BACKFILL TRENCH
09/27/2005 PLUMBING - GAS PRESSURE TEST TRINIVJR Approved IVRS - Inspection :*
11/10/2005 FIRE SPKLR - FINAL LTHOMAS Approved
11/10/2005 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
11/10/2005 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
11/10/2005 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
11/16/2005 ELECTRIC - ABOVE CEILING RMAJUTA Approved IVRS - Inspection :*
12/08/2005 PLUMBING - YARD WTR LINE/TEST TRINIVJR Approved IVRS - Inspection :*2" YARD WATER LINE FROM METER TO BLDG. SERVICE IS OK
OK TO BACKFILL THE TRENCH.
12/19/2005 FIRE - FINAL LTHOMAS Approved
12/19/2005 FIRE - ALARM FINAL LTHOMAS Approved
12/28/2005 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS 314.20
2) FILL UNUSED OPENINGS
3) MAINTAIN ALL CLEARANCES AT PANEL PER 110.26
4) WHERE IS TRANSFORMER GROUNDING ELECTRODE CONDUCTOR
5) PLEAS HAVE ELECTRICIAN PRESENT TO OPEN UP ELECTRICAL EQUIPMENT THESE HAVE BEEN ENGERGIZED WITHOUT INSPECTIONS
6) PLEASE PROVIDE ACCESS TO HIGH BAY LIGHTING TO INSPECT
7) PANEL DIRECTORY NOT CLEAR
8) PLEASE VERIFY COMPLETION OF INTERMEDIATE INSPECTIONS
9) CHECK ROOF AND OUTSIDE LIGHTS NEXT TRIP
12/30/2005 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*OK FOR FINAL C OF O
12/30/2005 MECHANICAL - ABOVE CEILING JMILITEL Approved
12/30/2005 MECHANICAL - INTERMEDIATE JMILITEL Approved
12/30/2005 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
1) MUST HAVE ALL OTHER FINALS AND C OF O APPROVALS PRIOR TO BLDG FINAL
2) NEED SIGNAGE AT RESTROOM DOORS
12/30/2005 PLUMBING - FINAL TRINIVJR Approved IVRS - Inspection :*
1) PLUMBING FINAL IS OK
2) OK FOR C OF O
12/30/2005 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection :*
12/30/2005 FRAMING AQUIROZ Approved IVRS - Inspection :*
12/30/2005 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
12/30/2005 U VALUE FOR WINDOW AQUIROZ Approved IVRS - Inspection :*
01/04/2006 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL
01/17/2006 ENGINEERING - FINAL NKALAHAR Approved SIDEWALKS IN
DOWNSPOUTS IN PLACE AND AWAY FROM PEDESTRIAN ACCESS (NO SPLASH BLOCKS)
01/17/2006 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
03/06/2006 PERMIT FINALED LJACKSON Approved