Permit: T03CM01875

Parcel: 123030590

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/03/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*OK FINAL
12/28/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS 314.20
2) FILL UNUSED OPENINGS
3) MAINTAIN ALL CLEARANCES AT PANEL PER 110.26
4) WHERE IS TRANSFORMER GROUNDING ELECTRODE CONDUCTOR
5) PLEAS HAVE ELECTRICIAN PRESENT TO OPEN UP ELECTRICAL EQUIPMENT THESE HAVE BEEN ENGERGIZED WITHOUT INSPECTIONS
6) PLEASE PROVIDE ACCESS TO HIGH BAY LIGHTING TO INSPECT
7) PANEL DIRECTORY NOT CLEAR
8) PLEASE VERIFY COMPLETION OF INTERMEDIATE INSPECTIONS
9) CHECK ROOF AND OUTSIDE LIGHTS NEXT TRIP