Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*OK FINAL | |
| 12/28/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS 314.20 2) FILL UNUSED OPENINGS 3) MAINTAIN ALL CLEARANCES AT PANEL PER 110.26 4) WHERE IS TRANSFORMER GROUNDING ELECTRODE CONDUCTOR 5) PLEAS HAVE ELECTRICIAN PRESENT TO OPEN UP ELECTRICAL EQUIPMENT THESE HAVE BEEN ENGERGIZED WITHOUT INSPECTIONS 6) PLEASE PROVIDE ACCESS TO HIGH BAY LIGHTING TO INSPECT 7) PANEL DIRECTORY NOT CLEAR 8) PLEASE VERIFY COMPLETION OF INTERMEDIATE INSPECTIONS 9) CHECK ROOF AND OUTSIDE LIGHTS NEXT TRIP |