Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) DWV WATER TEST IS OK 2) OVERHEAD WATER DISTRIBUTION IS OK 3) OK FOR DRY WALL |
|
| 06/13/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FEMALE ABS TREADED FITTING NOT PERMISSABLE IN INACCESSIBLE LOCATION. SEE INSTALLATION STD # 5 94 UPC PROHIBITED LOCATIONS. 2) STILL NOT TEST ON ABS. 3) TRAP PRIMER NOT INSTALLED PER PLAN-SEE DETAIL. |
|
| 06/03/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* / 1) REVIEW SECTION 15260 INSULATION ALSO DETAIL 208 ON P2.2BN. 2) ADA WTR CLOSETS TO HAVE FLUSH HANDLE ON WIDE SIDE. 3) EXTEND CO AT EWC TO FINISHED WALL IN AN APPROVED MANNNER SEE NOTE # 4 FROM 5/22/5. CONTRACTOR TO PAY RE-INSPECTION FEE |
|
| 05/22/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) NO SPEC BOOK ON SITE 2) PLUMBER TAPE NOT APPROVED STRAP 3) REVIEW 15.5 94 UPC HANGERS TO BE AT EACH CHANGE OF DIRECTION EACH CHANGE OF ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN 4 FEET BETWEEN HANGERS 4) ALL OF THE ABS TO BE TESTED, SEE DETAIL 206 P2.1 BN 5) SEE DETAIL 208 P2.2 BN 6) INSPECTION STOPPED |
|
| 05/19/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) GATES LOCKED, NO ACCESS |
|
| 05/16/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PLEASE HAVE APPROVED PLANS ON JOB PROVIDE MID STORY ANCHORS ON WAST VENTS & WATER. |