Permit: T03CM01875

Parcel: 123030590

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/20/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1) DWV WATER TEST IS OK
2) OVERHEAD WATER DISTRIBUTION IS OK
3) OK FOR DRY WALL
06/13/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) FEMALE ABS TREADED FITTING NOT PERMISSABLE IN INACCESSIBLE LOCATION. SEE INSTALLATION STD # 5 94 UPC PROHIBITED LOCATIONS. 2) STILL NOT TEST ON ABS. 3) TRAP PRIMER NOT INSTALLED PER PLAN-SEE DETAIL.
06/03/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999* / 1) REVIEW SECTION 15260 INSULATION ALSO DETAIL 208 ON P2.2BN. 2) ADA WTR CLOSETS TO HAVE FLUSH HANDLE ON WIDE SIDE. 3) EXTEND CO AT EWC TO FINISHED WALL IN AN APPROVED MANNNER SEE NOTE # 4 FROM 5/22/5. CONTRACTOR TO PAY RE-INSPECTION FEE
05/22/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) NO SPEC BOOK ON SITE
2) PLUMBER TAPE NOT APPROVED STRAP
3) REVIEW 15.5 94 UPC HANGERS TO BE AT EACH CHANGE OF DIRECTION EACH CHANGE OF ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN 4 FEET BETWEEN HANGERS
4) ALL OF THE ABS TO BE TESTED, SEE DETAIL 206 P2.1 BN
5) SEE DETAIL 208 P2.2 BN
6) INSPECTION STOPPED
05/19/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) GATES LOCKED, NO ACCESS
05/16/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :* PLEASE HAVE APPROVED PLANS ON JOB PROVIDE MID STORY ANCHORS ON WAST VENTS & WATER.