Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Closed
Type:
POOL - RESIDENTIAL
Address NEW:
10641 E ELKRIDGE PL
Apply Date:
10/10/2003
Applicant:
BLUE HAVEN POOLS *C
Description:
POOL:GUNITE TD#15-42-32
Contractors:
  • BLUE HAVEN POOLS *C

Permit Reviews

Permit Number - T03BU02644
Permit Status: Closed
Permit Description: POOL:GUNITE TD#15-42-32
Start Date Submittal Complete Date Status  
10/10/2003 POOL/SPA 10/10/2003 COMPLETED Review Details

Completed Inspections

Permit Status: Closed
Permit Number: T03BU02644
Permit Description: POOL:GUNITE TD#15-42-32
Total Completed Inspections - 5
Date Description Inspector Results Comments
11/26/2003 POOL/SPA HEATER RFREIDIN Approved IVRS - Inspection 0000*
11/26/2003 POOL/SPA ELECTRIC RFREIDIN Approved IVRS - Inspection 0000*/ 1) PLEASE LEAVE ELECTRIC LOAD CALC, FOR ENTIRE SERVICE LOAD IN PLAN TUBE AT NEXT INSPECTION 2) 50 AMP 2 POLE BREAKER FOR SPA IS PROTECTING #10 CU. WIRE, NEEDS TO BE INSTALLED PER U.L. LABEL ON SPA UNIT
11/26/2003 POOL/SPA PLUMBING RFREIDIN Approved IVRS - Inspection 0000*
11/26/2003 POOL/SPA PRE-GUNITE RFREIDIN Approved IVRS - Inspection 0000*
02/24/2004 POOL/SPA FINAL/BARRIER HPEDROZA Approved IVRS - Inspection 0000*/ 1) GFCI AT POOL EQUIPMENT WILL NOT TRIP, NOT WIRED PROPERLY 2) HOT AND NEUTRAL REVERSED

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW