Permit: T03BU02644

Parcel: 136321360


Addresses:

10641 E ELKRIDGE PL

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
02/23/2009 POOL/SPA ELECTRIC Approved
02/20/2004 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection 0000*/ 1) OUTLET BY DISCONNECT NEEDS TO GFCI PROTECTED 2) WROUGHT IRON WITHIN 5 FEET FROM WATERS EDGE MUST BE BONDED TO POOL 3) NORTH EAST CORNER OF BARRIER EXCEEDS 4" 4) FINAL WILL BE APPROVED WHEN ALL IS COMPLETE
11/26/2003 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection 0000*/ 1) PLEASE LEAVE ELECTRIC LOAD CALC, FOR ENTIRE SERVICE LOAD IN PLAN TUBE AT NEXT INSPECTION 2) 50 AMP 2 POLE BREAKER FOR SPA IS PROTECTING #10 CU. WIRE, NEEDS TO BE INSTALLED PER U.L. LABEL ON SPA UNIT