Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 02/23/2009 |
POOL/SPA ELECTRIC |
|
Approved |
|
| 02/20/2004 |
POOL/SPA ELECTRIC |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OUTLET BY DISCONNECT NEEDS TO GFCI PROTECTED 2) WROUGHT IRON WITHIN 5 FEET FROM WATERS EDGE MUST BE BONDED TO POOL 3) NORTH EAST CORNER OF BARRIER EXCEEDS 4" 4) FINAL WILL BE APPROVED WHEN ALL IS COMPLETE |
| 11/26/2003 |
POOL/SPA ELECTRIC |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLEASE LEAVE ELECTRIC LOAD CALC, FOR ENTIRE SERVICE LOAD IN PLAN TUBE AT NEXT INSPECTION 2) 50 AMP 2 POLE BREAKER FOR SPA IS PROTECTING #10 CU. WIRE, NEEDS TO BE INSTALLED PER U.L. LABEL ON SPA UNIT |