Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
| Date |
Description |
Inspector |
Results |
Comments |
| 02/23/2009 |
POOL/SPA FINAL/BARRIER |
|
Approved |
|
| 02/24/2004 |
POOL/SPA FINAL/BARRIER |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) GFCI AT POOL EQUIPMENT WILL NOT TRIP, NOT WIRED PROPERLY 2) HOT AND NEUTRAL REVERSED |
| 02/20/2004 |
POOL/SPA FINAL/BARRIER |
|
Denied |
IVRS - Inspection 0999* |
| 02/12/2004 |
POOL/SPA FINAL/BARRIER |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PLEASE READ ITEMS FROM LAST INSPECTIONS, PLEASE COMPLY 2) NEXT INSPECTION IF NOT CORRECTED, REINSPECTION FEE WILL BE ASSESSED |
| 01/29/2004 |
POOL/SPA FINAL/BARRIER |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) REMOVE BOND STRAP FROM NEUTRAL BAR 2) FROM LAST INSPECTION, ASKED FOR LOAD CALC. SERV. EQUIP. 3) U.L. LABEL ON UNIT HEAT PUMP REQUIRES CIRCUIT AMPACITY OF 40/36.9 AMPS, #10 EQUIP GRD. CONDUCTOR NEEDED FROM SERVICE TO DISCONNECT FOR HEAT PUMP 4) OWNER STATES THAT WATER PRESSURE, NOT HOLDING STEADY, PLEASE CHECK OUT, HAVE GUAGE HOLDING AT 25 POUNDS NEXT INSPECTION 5) 200 AMP BREAKER INSTALLED, NO LABEL ON SERVICE COVER, SHOWING SERVICE RATING 6) POOL BARRIER NOT COMPLETE REAR FENCE 7) PLEASE UNCOVER CONDUIT, HOME RUN AT SHED 8) #10 GRD CONDUCTOR LEAVE SERVICE PANEL, CAN'T FIND TERMINATION |