Permit: T02CM05589
Permit Details
Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
2312 N ROSEMONT BL #110
Address NEW:
2312 N ROSEMONT BL #110
Apply Date:
12/04/2002
Applicant:
LARRY CLICK
Description:
TI:OFFICE
Contractors:
- EPSTEIN FENTON L L C ,
Permit Reviews
Permit Number - T02CM05589
Permit Status: Expired
Permit Description: TI:OFFICE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/04/2002 | COMMERCIAL TI | 12/10/2002 | COMPLETED |
| 12/18/2002 | REVISION | 12/18/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02CM05589
Permit Status: Expired
Permit Description: TI:OFFICE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/04/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T02CM05589
Permite Description: TI:OFFICE
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2003 | SIGN - FINAL | N/A | Denied | IVRS - Inspection 0605$ |
Completed Inspections
Permit Status: Expired
Permit Number: T02CM05589
Permit Description: TI:OFFICE
Total Completed Inspections - 13
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2002 | PLUMBING - ROUGH, SOIL | TRINIVJR | Approved | IVRS - Inspection 0000* 1.) SOIL WATER TEST IS OK 2.) P.O.C. OF NEW BLDG. DRAIN TO EXSISTING BLDG. DRAIN IS OK 3.) OK TO BACKFILL TRENCH. 4.) NOTE: WILL REQUIRE A REVISED & APPROVED PLAN ON WASTE & VENT SYSTEM PRIOR TO NEXT INSPECTION. |
| 12/26/2002 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection 0000*1.) ABS DWV FOR HCWC, BAR SINK, LAV OK ABS DWV FOR ADDITIONAL SINK OK COPPER IN WALLS OK OK TO COVER WALLS. 2.) CLOSET FLANGE OK 3.) WATER HEATER EXCEEDS EIGHT FEET, WILL REQUIRE PERMANENT LADDER TO ACCESS AS PER 511.2 94 UPC. |
| 12/30/2002 | ELECTRIC - ABOVE CEILING | DSANTACR | Approved | IVRS - Inspection 0000*OK LIGHT FIXTURES EXCEPT NORTHWEST RESTROOM PLEASE NOTE THAN PLAN CALLS FOR WIRING TO BE IN 1/2" CONDUIT, USE OF MC MUST BE APPROVED BY ARCH. ALSO IN PATIENT CARE/EXAM ROOMS MUST COMPLY WITH ART 517-13 NEC. WIRING METHODS. |
| 01/02/2003 | FRAMING | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 01/03/2003 | SHEET ROCK NAILING | HLEYVA | Approved | IVRS - Inspection 0000* |
| 01/15/2003 | RIGHT OF WAY - FINAL | PWHIDDON | Approved | |
| 01/15/2003 | ENGINEERING - FINAL | LMAKUS | Approved | |
| 01/15/2003 | FIRE - FINAL | JEGAN | Approved | IVRS - Inspection 0000*OKAY FOR C OF O. |
| 01/15/2003 | PLUMBING - FINAL | JSTANLEY | Approved | IVRS - Inspection 0000*FINAL OK S.T.O.I. |
| 01/15/2003 | PLUMBING - PROGRESS | JSTANLEY | Approved | |
| 01/15/2003 | PLUMBING - ABOVE CEILING | JSTANLEY | Approved | |
| 01/15/2003 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection 0000*NOTE: SERVICE DISCONNECT WS NOT ACCESSABLE ABOVE DUE TO VEGITATION GROWN INTO WORKING SPACE AS DEFINIED BY CODE 110-26. |
| 01/17/2003 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection 0000*OK C OF O. |