Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Apply Date:
12/04/2002
Applicant:
LARRY CLICK
Description:
TI:OFFICE
Contractors:
  • EPSTEIN FENTON L L C ,

Permit Reviews

Permit Number - T02CM05589
Permit Status: Expired
Permit Description: TI:OFFICE
Start Date Submittal Complete Date Status  
12/04/2002 COMMERCIAL TI 12/10/2002 COMPLETED Review Details
12/18/2002 REVISION 12/18/2002 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T02CM05589
Permit Status: Expired
Permit Description: TI:OFFICE
Total Outstanding Activity Conditions - 1
Date Name
12/04/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T02CM05589
Permite Description: TI:OFFICE
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/15/2003 SIGN - FINAL N/A Denied IVRS - Inspection 0605$

Completed Inspections

Permit Status: Expired
Permit Number: T02CM05589
Permit Description: TI:OFFICE
Total Completed Inspections - 13
Date Description Inspector Results Comments
12/19/2002 PLUMBING - ROUGH, SOIL TRINIVJR Approved IVRS - Inspection 0000*
1.) SOIL WATER TEST IS OK
2.) P.O.C. OF NEW BLDG. DRAIN TO EXSISTING BLDG. DRAIN IS OK
3.) OK TO BACKFILL TRENCH.
4.) NOTE: WILL REQUIRE A REVISED & APPROVED PLAN ON WASTE & VENT SYSTEM PRIOR TO NEXT INSPECTION.
12/26/2002 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection 0000*1.) ABS DWV FOR HCWC, BAR SINK, LAV OK ABS DWV FOR ADDITIONAL SINK OK COPPER IN WALLS OK
OK TO COVER WALLS.
2.) CLOSET FLANGE OK
3.) WATER HEATER EXCEEDS EIGHT FEET, WILL REQUIRE PERMANENT LADDER TO ACCESS AS PER 511.2 94 UPC.
12/30/2002 ELECTRIC - ABOVE CEILING DSANTACR Approved IVRS - Inspection 0000*OK LIGHT FIXTURES EXCEPT NORTHWEST RESTROOM
PLEASE NOTE THAN PLAN CALLS FOR WIRING TO BE IN 1/2" CONDUIT, USE OF MC MUST BE APPROVED BY ARCH.
ALSO IN PATIENT CARE/EXAM ROOMS MUST COMPLY WITH ART 517-13 NEC. WIRING METHODS.
01/02/2003 FRAMING AQUIROZ Approved IVRS - Inspection 0000*
01/03/2003 SHEET ROCK NAILING HLEYVA Approved IVRS - Inspection 0000*
01/15/2003 RIGHT OF WAY - FINAL PWHIDDON Approved
01/15/2003 ENGINEERING - FINAL LMAKUS Approved
01/15/2003 FIRE - FINAL JEGAN Approved IVRS - Inspection 0000*OKAY FOR C OF O.
01/15/2003 PLUMBING - FINAL JSTANLEY Approved IVRS - Inspection 0000*FINAL OK S.T.O.I.
01/15/2003 PLUMBING - PROGRESS JSTANLEY Approved
01/15/2003 PLUMBING - ABOVE CEILING JSTANLEY Approved
01/15/2003 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection 0000*NOTE: SERVICE DISCONNECT WS NOT ACCESSABLE ABOVE DUE TO VEGITATION GROWN INTO WORKING SPACE AS DEFINIED BY CODE 110-26.
01/17/2003 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection 0000*OK C OF O.