Permit: T02CM05589

Parcel: 121130990

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/15/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
01/10/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK ABOVE CEILING.
1.) STILL NEED LETTER FOR M/C CABLE
01/03/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OKWALLS
1.) PLEASE SUPPORT OLD VDV CABLES UP OFF OF GRID.
12/30/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK LIGHT FIXTURES EXCEPT NORTHWEST RESTROOM
PLEASE NOTE THAN PLAN CALLS FOR WIRING TO BE IN 1/2" CONDUIT, USE OF MC MUST BE APPROVED BY ARCH.
ALSO IN PATIENT CARE/EXAM ROOMS MUST COMPLY WITH ART 517-13 NEC. WIRING METHODS.