Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
09/18/2001
Applicant:
D AND H AIR CONDITIONING CO,*C
Description:
REPLACE:HEAT PUMP (APA)
Contractors:
  • D AND H AIR CONDITIONING CO,*C

Outstanding Activity Conditions

Permit Number - T01ME00768
Permit Status: Expired
Permit Description: REPLACE:HEAT PUMP (APA)
Total Outstanding Activity Conditions - 1
Date Name
09/18/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01ME00768
Permite Description: REPLACE:HEAT PUMP (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
10/04/2001 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*1.) AC UNIT HAS A CONDENSATE TRAP BUILT INTO THE UNIT REMOVE EXTERNAL TRAP. 2.) PAINT EXPOSED PVC W/LATEX PAINT 3.) UNIT IS OVER FUSED. 30 AMP IS MAX FUSE SIZE. CORRECT & RECALL FOR INSPECTION.