Permit: T01ME00768

Parcel: 134090470

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/04/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) AC UNIT HAS A CONDENSATE TRAP BUILT INTO THE UNIT REMOVE EXTERNAL TRAP. 2.) PAINT EXPOSED PVC W/LATEX PAINT 3.) UNIT IS OVER FUSED. 30 AMP IS MAX FUSE SIZE. CORRECT & RECALL FOR INSPECTION.