Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
4004 S PARK AV
Apply Date:
12/05/2001
Applicant:
METRO PERMIT EXPRESS, INC
Description:
TI:COMMUNICATIONS CENTER INSTALLATION OF A/C EQUIPMENT AND DUCT

Permit Reviews

Permit Number - T01CM05890
Permit Status: Expired
Permit Description: TI:COMMUNICATIONS CENTER INSTALLATION OF A/C EQUIPMENT AND DUCT
Start Date Submittal Complete Date Status  
12/05/2001 COMMERCIAL TI 06/14/2002 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T01CM05890
Permit Status: Expired
Permit Description: TI:COMMUNICATIONS CENTER INSTALLATION OF A/C EQUIPMENT AND DUCT
Total Outstanding Activity Conditions - 1
Date Name
12/05/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01CM05890
Permite Description: TI:COMMUNICATIONS CENTER INSTALLATION OF A/C EQUIPMENT AND DUCT
Total Outstanding Inspections - 6
Last Inspection Date Description Inspector Results Comments
MECHANICAL - ABOVE CEILING N/A Not Inspected
FIRE - FINAL N/A Not Inspected
07/31/2002 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection 0920* DENIED 1.) NEED GROUNDING BUSHINGS AND BONDING JUMPERS THROUGHOUT ON ALL IMPAIRMENT TO THE BONDING CONTINUITY OF ALL CONDUIT TERMINATION WHICH CONTAIN CIRCUITS OF OVER 250 VOLTS TO GROUND. 2.) LOOSE FITTING THROUGHOUT. 3.) IMPROPER CLEARANCE IN FRONT OF DISCONNECT 110-26. 4.) NEED BETTER ACCESSIBLITY FOR WEATHER PROOF BOX 5.) PULL BOXER, JUNCTION BOX TO BE SIZED PER ARTICLE 370. INCLUDER MEMBER OF CONDUCTOR IN BOX. 6. PLEASE IDENTIFY JUNCTION BOXES AND DISCONNECT 7. NEED BUSHINGS THROUGHOUT 8.) POSITIVELY ATTACH ALL BOXES TO FROMING USING APPROPRIATE HARDWARE AND SUPPORT ALL CONDUIT W/PROPER FITTINGS AND AT PROPER INTERVALS.
07/31/2002 ELECTRIC - ABOVE CEILING N/A Denied IVRS - Inspection 0999*
07/31/2002 MECHANICAL - INTERMEDIATE N/A Partial Approval
09/06/2002 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection 0000*

Completed Inspections

Permit Status: Expired
Permit Number: T01CM05890
Permit Description: TI:COMMUNICATIONS CENTER INSTALLATION OF A/C EQUIPMENT AND DUCT
Total Completed Inspections - 5
Date Description Inspector Results Comments
06/19/2002 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved IVRS - Inspection 0000*
09/05/2002 BUILDING - FINAL LHANLY Approved IVRS - Inspection 0000*THIS IS FOR AN A/C INSTALLATION.
09/05/2002 FRAMING LHANLY Approved IVRS - Inspection 0000*
09/06/2002 FIRE SPKLR - FINAL LTHOMAS Approved
09/12/2002 ELECTRIC - FINAL JORTA Approved IVRS - Inspection 0000*