Permit: T01CM05890
Permit Details
Apply Date:
12/05/2001
Applicant:
METRO PERMIT EXPRESS, INC
Description:
TI:COMMUNICATIONS CENTER INSTALLATION OF A/C EQUIPMENT AND DUCT
Permit Reviews
Permit Number - T01CM05890
Permit Status: Expired
Permit Description: TI:COMMUNICATIONS CENTER INSTALLATION OF A/C EQUIPMENT AND DUCT
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
12/05/2001 | COMMERCIAL TI | 06/14/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01CM05890
Permit Status: Expired
Permit Description: TI:COMMUNICATIONS CENTER INSTALLATION OF A/C EQUIPMENT AND DUCT
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
12/05/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01CM05890
Permite Description: TI:COMMUNICATIONS CENTER INSTALLATION OF A/C EQUIPMENT AND DUCT
Total Outstanding Inspections - 6
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
MECHANICAL - ABOVE CEILING | N/A | Not Inspected | ||
FIRE - FINAL | N/A | Not Inspected | ||
07/31/2002 | ELECTRIC - INTERMEDIATE | N/A | Denied | IVRS - Inspection 0920* DENIED 1.) NEED GROUNDING BUSHINGS AND BONDING JUMPERS THROUGHOUT ON ALL IMPAIRMENT TO THE BONDING CONTINUITY OF ALL CONDUIT TERMINATION WHICH CONTAIN CIRCUITS OF OVER 250 VOLTS TO GROUND. 2.) LOOSE FITTING THROUGHOUT. 3.) IMPROPER CLEARANCE IN FRONT OF DISCONNECT 110-26. 4.) NEED BETTER ACCESSIBLITY FOR WEATHER PROOF BOX 5.) PULL BOXER, JUNCTION BOX TO BE SIZED PER ARTICLE 370. INCLUDER MEMBER OF CONDUCTOR IN BOX. 6. PLEASE IDENTIFY JUNCTION BOXES AND DISCONNECT 7. NEED BUSHINGS THROUGHOUT 8.) POSITIVELY ATTACH ALL BOXES TO FROMING USING APPROPRIATE HARDWARE AND SUPPORT ALL CONDUIT W/PROPER FITTINGS AND AT PROPER INTERVALS. |
07/31/2002 | ELECTRIC - ABOVE CEILING | N/A | Denied | IVRS - Inspection 0999* |
07/31/2002 | MECHANICAL - INTERMEDIATE | N/A | Partial Approval | |
09/06/2002 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection 0000* |
Completed Inspections
Permit Status: Expired
Permit Number: T01CM05890
Permit Description: TI:COMMUNICATIONS CENTER INSTALLATION OF A/C EQUIPMENT AND DUCT
Total Completed Inspections - 5
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2002 | EXCAVATION/LAYOUT REBAR & ZON | LHANLY | Approved | IVRS - Inspection 0000* |
09/05/2002 | BUILDING - FINAL | LHANLY | Approved | IVRS - Inspection 0000*THIS IS FOR AN A/C INSTALLATION. |
09/05/2002 | FRAMING | LHANLY | Approved | IVRS - Inspection 0000* |
09/06/2002 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
09/12/2002 | ELECTRIC - FINAL | JORTA | Approved | IVRS - Inspection 0000* |