Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/12/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/05/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*J-BOX ABOVE CU-1 STRANDED GRD WIRE NEEDS STAKON 2.) WHERE 1" CONDUIT GOES THUR CEILING INSIDE AT HALL CORRECT STRAP HOLDING CONDUIT BEFORE IT ENTERS CEILING. 3.) DISCONNECT FC-2 NEED GROUNDING BUSHING ON CONDUIT ENTRIES AS PER #1 ABOVE, WHERE 480 V CONDUCTORS GO THUR CONCENTRIC ENTRIES NEED GROUND BUSHINGS. |