Inspection Status: Denied
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/31/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0920* DENIED 1.) NEED GROUNDING BUSHINGS AND BONDING JUMPERS THROUGHOUT ON ALL IMPAIRMENT TO THE BONDING CONTINUITY OF ALL CONDUIT TERMINATION WHICH CONTAIN CIRCUITS OF OVER 250 VOLTS TO GROUND. 2.) LOOSE FITTING THROUGHOUT. 3.) IMPROPER CLEARANCE IN FRONT OF DISCONNECT 110-26. 4.) NEED BETTER ACCESSIBLITY FOR WEATHER PROOF BOX 5.) PULL BOXER, JUNCTION BOX TO BE SIZED PER ARTICLE 370. INCLUDER MEMBER OF CONDUCTOR IN BOX. 6. PLEASE IDENTIFY JUNCTION BOXES AND DISCONNECT 7. NEED BUSHINGS THROUGHOUT 8.) POSITIVELY ATTACH ALL BOXES TO FROMING USING APPROPRIATE HARDWARE AND SUPPORT ALL CONDUIT W/PROPER FITTINGS AND AT PROPER INTERVALS. |